Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

How does frequency affect KVA rating of a transformer?
If a 500 kva, 400 v, 60 hz t/f is to be operated on 50 hz
frequency then how will its KVA rating change?
a-increase
b-decrease
c-remains same
Also explain why do u think like that.

Answer Posted / rajendra kumar

If a 500 kva, 400 v, 60 hz t/f is to be operated on 50 hz
frequency then how will its KVA rating change?
expl-
kva rating depends upon V*I.
flux is same for both coil,
V1=4.44.N.f.phi
phi=k.V1/f=k.400/60=6.6
phi2/phi1=v1*f2/V1*f1=50/60=0.833
phi2=phi*0.833
V2 (sencondry side)=4.44 N2.f.phi2(at 50 hz)
=4.44.N2.f1*phi1
i.e no effect on voltage but flus has decreased means current will be decrease by factor 0.833.that is KVA=V*I2=V*I1*0.833 (decreases)

Is This Answer Correct ?    7 Yes 1 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

SIR, GIVE ME OPGW SAG CALCULATION FORMULA I AM DAE ELECTRICAL. THANKS

6805


Difference between low impedance and high impedance Restricted Earth Fault

3111


what is Anti-pumping?

1920


What is the effect of positive feedback on the stability of the systems?

1073


which protection used in power plant?

1937


what is the meaning of neutral displacement ???

2726


No load tap changing transformer working

1631


how to set the time in digital timer ?

2003


Why hydropower is called renewable source of energy?

1039


how to calculate

1676


A generating system will have a total capacity of 300 MW. Find the probable forced outage when the capacity is supplied by two 150 MW units. The operating probability of all units is P=0.98 and forced outage probability rate Q =0.02 .

2624


I am having dual speed motor of cromton greaves make of 3.7 KW -1400 rpm and 5 KW - 900 rpm. Please let me know groups and winding connction for rewinding purpose.

1910


How time response of the system is divided?

1180


Is there a diode made that works with AC 120 volt 20 amp? If so can it completely stop all current flow in 1 direction at all times?

6693


how to set relay setting? and example calculation...

2022