How does frequency affect KVA rating of a transformer?
If a 500 kva, 400 v, 60 hz t/f is to be operated on 50 hz
frequency then how will its KVA rating change?
a-increase
b-decrease
c-remains same
Also explain why do u think like that.
Answer Posted / rajendra kumar
If a 500 kva, 400 v, 60 hz t/f is to be operated on 50 hz
frequency then how will its KVA rating change?
expl-
kva rating depends upon V*I.
flux is same for both coil,
V1=4.44.N.f.phi
phi=k.V1/f=k.400/60=6.6
phi2/phi1=v1*f2/V1*f1=50/60=0.833
phi2=phi*0.833
V2 (sencondry side)=4.44 N2.f.phi2(at 50 hz)
=4.44.N2.f1*phi1
i.e no effect on voltage but flus has decreased means current will be decrease by factor 0.833.that is KVA=V*I2=V*I1*0.833 (decreases)
| Is This Answer Correct ? | 7 Yes | 1 No |
Post New Answer View All Answers
SIR, GIVE ME OPGW SAG CALCULATION FORMULA I AM DAE ELECTRICAL. THANKS
Difference between low impedance and high impedance Restricted Earth Fault
what is Anti-pumping?
What is the effect of positive feedback on the stability of the systems?
which protection used in power plant?
what is the meaning of neutral displacement ???
No load tap changing transformer working
how to set the time in digital timer ?
Why hydropower is called renewable source of energy?
how to calculate
A generating system will have a total capacity of 300 MW. Find the probable forced outage when the capacity is supplied by two 150 MW units. The operating probability of all units is P=0.98 and forced outage probability rate Q =0.02 .
I am having dual speed motor of cromton greaves make of 3.7 KW -1400 rpm and 5 KW - 900 rpm. Please let me know groups and winding connction for rewinding purpose.
How time response of the system is divided?
Is there a diode made that works with AC 120 volt 20 amp? If so can it completely stop all current flow in 1 direction at all times?
how to set relay setting? and example calculation...