1 ton AC takes how much current( starting & stable)
Answer Posted / tech mech
Check the Specification sheet of the Air-conditioner for wattage consumed or running current in Amperes. Starting current for compressor motors can be safely assumed as 3.5 times the running current. MCB (breaker) rating should be 1.5 times the max current required that is the starting current. So, Breaker rating should be 5-6 times Aircon running current. This is unique to appliances with motors like Refrigerators, Air conditioners, Washing machines, water pumps etc.,
Is This Answer Correct ? | 2 Yes | 4 No |
Post New Answer View All Answers
How to calculate the efficiency of Turbo Generator(Alternator) in general....?
What are the advantages of thermal power plant?
draw the block diagram of fire alarm?
how ct burden,magnetising current,ratio and knee point voltage are related & derived
what is PWM in IGBT and how it works for drive.?
Why AC & DC capacitor are use in UPS ??????????????????
Dear sir, iam completed iti ncvt electrician 2000-2002 & diploma electrical eng completed 2008-2010 distance education in rvd university, still i got B licences only but my working company want C licences, how to i get c licencese pls reply me iam in critical situation thank you karthick 9841637803
is there any current and voltage drop on liquid resistance starter water/soda tank ?
What is real time power factor control panel(RTPFC)?
why does a dc machine has high efficiency while working as a generator than as a motor ..
please forward me the type of questions which would rise while me attending to 33KV Electrical License to my mail ID:vadrevu_raghava@yahoo.co.in
What are the advantages and disadvantages of open loop control system?
234 MVA Generator 3 phase Short circuit current Values required? Gen set Rating-234 MVA, Gen Voltage-18kv, PF;0.8, Xdv:23.5 %, Transformer Rating-18/380KV, 680MVA,Yndd1 two winding, Step up TR, ZT:35.50 %,X/R 4.33 Gen CB Position, CB open ,Disconnected open, Generator Running Voltage 18 Kv, Bi mistakes generator side earth switch Closed during that time short circuit current level in 3 Phase required, and how to test on site 234MVA Generator Short circuit current,
Discuss about gear cutting machines.
why asa method ZPF method is more accurate than ASA method?