3 phase supply is there Total kw 100 howmuch cable put the load
Answer Posted / khaled shaban
you have to calculate your ampere by using below equ.
I=P/Sqrt(3)*V*P.F
after that you have to select circuit breaker; after selection of CB check cable size referring to cable ratings as per manufacturer.
e.g. Volt 380V, with 100Kw and consider P.F=0.8
current will be 190A
cable should handle more than 190A, but first you have to choose MCCB for this load; the standard for your selection should be as following:
MCCB size = I*1.25 (1.25 at least)
so MCCB will be more than 237.5A (for standard MCCB you will select 250A)
hence your MCCB is 250A, your cable should be more than 250A.
As per cable manufacturer rating in my country, cable size should be (3*120+70)mm2 laid in duct, but in case if this cable laid in ground; cable size will be (3*90+50)mm2.
| Is This Answer Correct ? | 4 Yes | 0 No |
Post New Answer View All Answers
hi , i have 150 kw loud and we need 50 m cabil,i want to know wich size cabil we use. thanks
According to underground cables a) stress b/w sheath & conductor is high b) inrush of core & conductor
why magnet has north and south poles only why not east and west and why we are considering as north and south poles? why cant we consider as east and west?
what is smart grid? why we use it? explain in detals bcoz i want give presentatin from it....
what is the concept of directional power?
Why LED light has advantage of rapid reflection ,although other lights alse reflect.? and this light is considered to be best for transmission usage in case of Free optics
How to design inductive load for 3 phase 440v and maximum 5 amps for star or delta? Can we use a 15kW, 1450rpm motor for 15kW, 960rpm apllication?If yes.how......n.if thesame motor used what`s it`s sideeefect.
What are the different types of transformers?
1. A 380 / 220 V r.m.s. 3-phase 4-wire circuit carries loads of 8 + j8.1 ohm; 4 + j4.1 ohm; and 2 +j2.1 ohmin the three phases respectively. The length of the circuit is 100 m, and the resistivity of the phase conductors is 0.0005 Ω/m. The neutral conductor is of the same size as the phase conductors. a) Select a reference angle 0for the first phase. Then write down the three phase voltages in both polar format and complex number format. b) Make appropriate assumptions, and take temperature effects on resistance is insignificant. Calculate the currents in the three phases. (Note: Determine conductor resistance, and apply Kirchhoff’s Voltage Law) Based on the result, suggest a main switch rating for the circuit. c) Show your preferred direction of neutral current in a diagram, and then determine its value. (Note: Apply superposition principle, and Kirchhoff’s Current Law) Use its magnitude to show that in this circuit, the unbalanced load may increase the voltage drop in some of the phases. (Note: Also observe the common volt drip in neutral) State your assumptions, if there are any. d) Suddenly the neutral wire of the circuit is broken. Estimate the new currents in the first phase, i.e. Phase L1. State your assumptions, if there are any.
How to calculate no of EARTH PIT? Describe the formula as per IS standard?
If one lamp connects between two phases it will glow or not?
In which working principal temperature transmitter work.explain in detailed.
Draw a SLD for main panel for school having connected load of 1200kw and emergency generator 200kw.also show the increase of additional load of chiller 225kw in the lv panel indicating meter postion size of transformer ,cables and capacitor bank.
what is the synchronous timer ? and it applications.
WHAT IS MOBILE SUB-STATION? & REALLY BENEFIT IN INDIA