I have 1500KVA transformer ,How much Maximum KW Load is
allowed?
Answer Posted / plemieux m. el.
To calculate full load current, use this formula:
Amps = KVA÷Volts÷1.732x1000
| Is This Answer Correct ? | 0 Yes | 1 No |