how can we find a burden of potential transformer? what
does it effects? how can we calculate rated load of it?
Answer Posted / tuktuk
Dear Mr.Raghavendran,
Thank you for your answer, I have the same problem but after reading your answer I still have some concerns.
I am really confused. In this case, we do not know the rated burden of the VT. Now we have to calculate the total burden and then selecte the rated value from IEC standards.
__Ztotal, which you mentioned above, is in Ohm or VA?
__Zsec and Zrelay we can get the value from manufacturer but Zlead, is it calculated by this formula: Zlead= (p*L)/S
(where: p is specific resistivity of copper in ohm.mm^2/m; L is length of lead between the PT secondary and the relay in meter; S is the section of lead in sqmm)? Is this true?
__I dont know how can we get secondary current Isec? (I guess Isec=Usec/Zt, isn't it?)
__And Burden in VA = Zt*Isec. As Ohm law, we have P=VI=RI^2=U^2/R, I do not understand the formula that you used to calculate Burden of VT in VA
Hope that you could help me to solve this stuck in my head.
Thank you.
| Is This Answer Correct ? | 0 Yes | 0 No |
Post New Answer View All Answers
After doubling voltage from solar cells & use step down voltage transformer can we get high current output with low voltage.
What is pd controller?
BRIEFLY EXPLAIN THE STORAGE CLASSES AND THEIR TYPES IN C
What is the Designing & Selection Procedure for a DG/Transormer of rated capacity?
when elecromagnatic waves are propogated in a wave guide?
What is the IS standard for MCCB to be use (As per capacity of AMP)& for ACB also.
for a 500 KVA connected load, I calculated 30% of capactor for power correction. Even after using 225 KVR capactor PF is not improving. What could be reason for low Phase correction factor?
What happen Grid EARTH plat got cut.
plz send me the procedure and syllabus for mseb exam
What is the high series capacitance winding on high voltage power transformer ?
hi frnds...pls send me aptransco previous papers .....pls..pls,,,(madhar.rocking@gmail.com)and suggest me some websites
There is any especial requirement for motor to drive through with VFD?
Pleae send me last 5 years of Question book about RRB chennai.
sir, what is the importance of Fault MVA. how to calculate fault mva of 33kv substation connected by 6.5 km line(single circuit with equal spacing) with 110/11kv transformer in 110kv susbstation.the fault mva on 11 kv bus in 110kv susbstation is 208mva.
internally connection of photvoltic module