Why two main buses and one transfer bus scheme not using
for 400kV switchyard
Answer Posted / jkrocks
DMT scheme is used earlier in 400kV System but all new 400kv ss are made on one & half breaker scheme. it has many advantages over DMT scheme.
more reliable than DMT each time line or ICT remain connected through both buses I & II, reduces numbers of confusing isolator in system, reduce additional bus.
If one bus trip due to any fault , lines are transformer connected to that bus remains charged through another bus by means of Tie CB.
Only disadvantage is that this system require three breaker for 2 lines or transformer.
But It is nothing against lots of advantages of One & Half Breaker Scheme.
Is This Answer Correct ? | 2 Yes | 0 No |
Post New Answer View All Answers
What does the letter CTNM in negative phase sequence relay means?
can we install HT panel & LT panel side by side or how much clearance is required ?
Explain the working principle of Synchronous Generator and Assynchronous generator?
1))why we run three phase or three different circuit from a single conduit 2)) why not two circuit of different phase run in same conduit?? and why we run same three cicuit of same phae run in single conduit??
Sir, My doubt on cable sizing calculation, Load:74 KW calculated cable 1 run 50mm2. Now client asking us to reduce cable size by increasing runs. Sir, My question now when my mind strikes with 2 options 1) Divide load 74/2 = 36 and calculate cable for 36+36 making it 2 runs or 2) Simply i can divide 50mm2 /2 ie. 2 runs of 25mm2 Please suggest me sir
Why neutral cable carry current.
PLS MENTION QUESTIONS ASKED IN IOCL INTERVIEW FOR ELECTRICAL EGG??
why do we carry out winding resistance test?
what is earthing.how we make it,describe briefly.
define displacement & magnitude ?
Why slip ring ind. motor power consumption is low compare to induction motor .same 90 kw motor used same load output
Define characteristics impedance?
why should the lowest unit of a testing transformer ( cascaded transformer ) have higher power rating??
how to determine the cable size...pls explain me with the formula taking particular load....does the factors like impedance & short circuit rating influence the cable size, if so how....
our industries ht line so power fluctation(once drop of power please rectify causes