Sir We have a REF relay connected to 10MVA(Y-Y) Transformer.on
External earth fault REF relay trips along with earth fault
relay.The REF relay has no complant as we tested relay.Why is
it happening?
Answer Posted / k.prakashchandra
Also may be due to 1 .reverse connection of NCT leads ( Unbalanced current of lines and NCT current add to each other ). 2. Low saturation point of NCT as Kv of bushing NCT is usually less than that of line CTs
| Is This Answer Correct ? | 0 Yes | 0 No |
Post New Answer View All Answers
importance of reactive power management
wat is d diffr btw shunt coil and trip coil in VCB?
What happened if C.T mount at any cable or Bus bar in wrong direction . C.T going on proper work or not . C,T direction is essential thing to properly work.
Single phase and threephase power calculation
why occ characteristics curve in not tracing back when we are bringing back the rhoestat?
in electrical control panel. how can i choose the cable rating. (example - 11kw motor, 18-25A mpcb}
what is the use of Auto re-closer?
how we decide wire gauge for ac or dc coil and what is the basic diff. B/w these two coil?
Define filter?
5.WHICH TYPE WELDING PROCESSES USES NON CONSUMABLE ELECTRODE.........
Earth is a conductor or load?then ammeter connect to 3- phase supply,it shows the measurents or not?
my UPS suddenly goes off and all panel light also blow off.This happens even main electric supply is not interrupted.After some time it automatically starts functioning normally.Batteries are new.
we specify current in case of feeder but in case of distributor voltage, why?
How to check 11000/1.732 to 110/1.732 Potentila transformer (PT)?
i want to know about torque of slip ring induction motor