we are used SAMSON 3730 Smart positioner.please tell me how to calibration this.
Answer Posted / chanchal
at first check the air supply.if it is ok then
feed the 4mA by using calibrator in i/p converter of positioner. if valve is zero position(fully closed) then its ok.if valve is not in zero position(fully closed) then set the zero position in positioner by using zero point screw.
next feed the 20mA by using calibrator in i/p converter of positioner.if valve is 100% open then its ok.if valve is not 100% open. then adjust the span setting by using span screwin positioner.
then check 25%,50%,and 75% open position in valve by feeding 8mA,12mA,and 16mA by using calibrator in same way.
| Is This Answer Correct ? | 4 Yes | 5 No |
Post New Answer View All Answers
how to calculate the total flow in square root
find the kp ki kd from the transper function G(S)=29.44s+04707/1.5349s2+s
Please any one can provide latest aptitude test,technical test and interview questions for tata consulting engineering (TCE) i need it asap thanks in advance
Which tank weighing system is better to install (Accuracy point of view) 1) Tank weighing system with 3 load cell or 2) Tank weighing system with 4 Load cell
Can please tell mi about SIOS, PRM, SERVER, and what is the diference between PIN LAN, PCS LAN,APC Server, and please send the Doc if possible for referance,mail id patil_amit17@yahoo.com
What types of Instrumentation Related Questions can an Interviewer ask in a Telephonic Interview ?
Describe how to use megger to measure the earth resistance and insulation resistance
what are the steps I have to deal with?
when the instrument tapping on pipe line is located below and transmitter is located above the tapping point for liquid service transmitter, what should we do, is there any additional drain valve is required??
what effects a surging can produce in the compressor
Calibration procedure for water rotameters
What is mean by analytical instrumentation?
Draw a P& ID showing – orifice flange, plate, dp transmitter, isolation & bypass valves and tubing.
What is the difference bitween control net scaner and device net scaner
How to Calibrate Interface Level Troll in field