what is the need of reactor in between the transmission line?..like powergrid like that..
Answer Posted / sauvik biswas
With the fast expanding power system, the fault level (i.e. the power available to flow into a fault) is
also rising. The circuit breakers connected in the power system must be capable of dealing with
maximum possible short-circuit currents that can occur at their points of connection. Generally, the
reactance of the system under fault conditions is low and fault currents may rise to a dangerously high
value. If no steps are taken to limit the value of these short-circuit currents, not only will the duty
required of circuit breakers be excessively heavy, but also damage to lines and other equipment will
almost certainly occur.
In order to limit the short-circuit currents to a value which the circuit breakers can handle, additional
reactances known as reactors are connected in series with the system at suitable points. A
reactor is a coil of number of turns designed to have a large inductance as compared to its ohmic
resistance. The forces on the turns of these reactors under short-circuit conditions are considerable
and, therefore, the windings must be solidly braced. It may be added that due to very small resistance
of reactors, there is very little change in the efficiency of the system.
Advantages
(i) Reactors limit the flow of short-circuit current and thus protect the equipment from overheating
as well as from failure due to destructive mechanical forces.
(ii) Troubles are localised or isolated at the point where they originate without communicating
their disturbing effects to other parts of the power system. This increases the chances of
continuity of supply.
(iii) They permit the installation of circuit breakers of lower rating.
| Is This Answer Correct ? | 0 Yes | 0 No |
Post New Answer View All Answers
what is meant by tranformer impedance?
can any one provide me a connection wiring diagram for a DG set control panel along with BOM?
Application Comparison between 22KV (UE)and 33KV (E) system. Are we allowed to use 33KV (E) cable in lieu of 22KV (UE) cable. What are the technical disadvantages.
Why are cables rated for 40 KA for 0.25 Sec fault current rating?
DEAR SIR/MADAM,CLEARLY EXPLAIN ABOUT CRAWLING AND COGGING EFFECTS IN INDUCTION MOTOR.
how to calculate the change over time for star delta starter for different KW motor?
what is under coal gassification?
Vibromotor 252MV 1/4HP2P..what is mean by 252MV?
How to decide whether A / B / C / D curve type MCB should be used?
Role of active and reactive Power sharing in between two synchronized Generators, Droop Setting role ?
hr round
Why is the air gap between the pole pieces and the armature kept very small?
What does quality factor depend on in resonance?
what is the mechanical safety of DG ?
does buccholz in a transformer use batteries