when we are using HART COMMUNICATOR why we are using 250 ohm
resistance while using HART COMMUNICATOR.
Answer Posted / vinodkumar
when calibrating an hart transmitter in lab, we need a loop resistance between 250 ohms & 600 ohms, because without a resistor the HART communicator did not communicate with the transmitter. Because transmitter is a high impedance circuit with respect to the HART communicator. When HART communicator try to communicate with transmitter by producing a digital signal, the signal gets grounded through power supply and thus the signal didn't enter the transmitter without the resistor. When resistor is added, the transmitter become a low impedance circuit with respect to the resistor, so the signal produced by the HART communicator SHOULD have pass through the transmitter and so does the communication between HART communicator and HART Transmitter. Without the resistance between 250 ohms and 600 ohms the HART communicator did not communicate with Transmitter.
But in analog transmitters exact 250 ohms is used to convert 4 - 20mA to 1 - 5V respectively. For this only and exact 250 ohms is needed
| Is This Answer Correct ? | 5 Yes | 0 No |
Post New Answer View All Answers
we are using centum vp as monitoring with Dell precision work station T3600 but some times PC(s) are restarted automatically . how we can solve this problem? thanks
What is super thermocoupal?
god evening sir i am studying m.sc(tech)electronics &instrumention.am i elegible to all industies
Can I route 110 VDC and 24 VDC in a same Duct for our Interposing relay cabinet? IF yes or NO Please provide me IEEE Std. for the same. Please i required it on Urgent basis, i need to design IRP Cabinets and we have MCC 110VDC and Our Coil side is 24VDC, Please help as soon as possible.
the whole paper was based on Transducers..questions like define repeatability, error,accuracy,precision..den there were many q. on the conversion of Pa to mmHg and other units.. also..der wer few Q. on some level sensors(with diagram)
sir, i preparing hpcl,ongc,barc,hal exams(instrumentation engg)pls send a placement papers
What is loop1 and loop2 in MTS LT?
Who to difference between analog in & analog out in dcs?
Punj lloyd is coming in our Jadavpur Universtiy campus for campus placement. Please send me some hints about the writtend exam. My email id is subratafriends@gmail.com
POSSITIVE PULSE IS APPLIED TO AN INVERTER INPUT.THE TIME FROM THE LEADING EDGE OF THE INPUT TO THE LEADING EDGE OF THE OUTPUT IS 10 ns. THE TIME FROM THE TRAILING EDGE OF THE INPUT TO THE TRYLING EDGE OF THE OUTPUT IS 8 ns. WHAT ARE THE VALUES OF tPLH and tPHL?
hello sir/madam, I,Subramanian need 5yrs placement papers of officer trainee of Instrumentation technology.pls send to this mail id mani_nxtgen@yahoo.co.in please do the needful. with regards, subramanian.v
please tel me the calibration of pneumatic controler.
what is sliding spool valves?
how to convert MA in to measuring values..and how mwasuring values into MA ?..plz ansr.i have intervw
principle of dead weight tester ?