What is scale factor of proximitor & unit of the viabration.
Answer Posted / s.seshasayee
The Proximitor is designed to give known output voltage changes equal to known gap changes. This is called a SCALE FACTOR. For the proximity transducer system the standard scale factor is set at 200 millivolts per mil (200mV/mil). Scale factor information can be found on the nameplate attached to the Proximitor. Scale factors are linear for a minimum of 80 mils within the systems linear range.
Average Scale Factor (ASF) =
change in gap voltage/change in gap = 18-2/0.08in =200mV/mil
| Is This Answer Correct ? | 3 Yes | 1 No |
Post New Answer View All Answers
when the instrument tapping on pipe line is located below and transmitter is located above the tapping point for liquid service transmitter, what should we do, is there any additional drain valve is required??
need to calculate flow rate with the help of dp range and orifice bore dia and size. range is 0 to 400 inwc and orifice size is 12 inch 150 # rf and bore dia is 7.180 inch. need to calculation for flow rate
In turbine, what does term CDP, NI, NH, HSSOC, means
why we are using digital signals for I/O & how to measure this signals is getting or not ?
How to convert milliampares into flow??
I have 0.75mm sq multicore cable (IS type) , can use instead of same type but 1.5 sq mm cable ? Note : The distance is around about 150 meter.
which processor is used in dcs.
What is feed factor and its Importance in cement industry? How we can solve feed factor?.
When doing a liquid seal on a differential flow transmitter , most of the time the sealing liquid will be heavier then the process fluid. For wich application will the sealing liquid be lighter than the process fluid if transmitter is mounted below the process line.
flow transmitter formula?
ORP sensor working principle?
what is sliding spool valves?
in sulfur process what is material of impulse line we use to connect with transmitter ? and does teflon affected by sulfur?
give some question relative instrument fitter?
What is intrinsically safe system?