what will be the output of the temparature transmitter if
temp is 120 degre celcius.
Answer Posted / g.navaneethan
If transmitter is calibrated for 0 - 200 deg.C then
(120/200)*16 4
9.6 4
= 13.6 ma
Is This Answer Correct ? | 1 Yes | 1 No |
Post New Answer View All Answers
How does temperature bath work? How does coil gets heated only by applying some current?
What is cut off relay? And why use in PLC and DCS?
What are different types of orifice plates? State their uses.
I have a Control VAlve having size of 2 ".Only the known parameter is Pressure drop . Its 2 Kg. Then How to calculate control valve sizing means Cv.
Actual using of tube bender to bend 2 opposite 90 deg at correct measurement center to center of tubing.
i want formula for flow control.am doing project in flow control using orifice . i know value of the flow level(Q) . upstream(p1) pressure, orifice diameter(Do) , pipe diameter(Di) and oil viscosity(Vi) how can i calculate downstream pressure
how does we calibrate a square root flow transmitter ,give an example and explain it step by step like range calculation , calibration hook up series connection , zero check , and how to apply pressure , and if not geting proportional output then what should we do ?
WHAT IS THE DIFF. BETWEEN SKIN TEMPERATURE AND PASSES TEMPERATURE..?
How does a single acting, spring return ball valve actually work? Does it require continuous air supply?
why I need valve guard and whats different between guard and positioner ??
why is an oxygen sensor used in a boiler stack
In a gas over oil actuator, after the opening/closing of valve, how the gas is vented out? How does the hydraulic/gas circuit function?
the output of the common trasmitter protocol in qatar gas are the following
Can I route 110 VDC and 24 VDC in a same Duct for our Interposing relay cabinet? IF yes or NO Please provide me IEEE Std. for the same. Please i required it on Urgent basis, i need to design IRP Cabinets and we have MCC 110VDC and Our Coil side is 24VDC, Please help as soon as possible.
Why boiler chimney area oxyden sensor fixing?