Answer Posted / s kannan
MF is not for panels for relays and meters only. Meters will be connected with CT and PT's secondary. If we want to calculate MF for meters like Voltmeter and Ammeter Just follow the formula Mf= CT Ratio X PT Ratio.
Eg:
CT Ratio: 600-300/1-1A(Adopted ratio is 300A as primary) PT Ratio: 33KV/rt3/110V/rt3/110V/rt3
Then MF:(300/1)X(33000/rt3/110/rt3)
(300/1)X(33000/1.732X1.732/110)
(300)X(33000/110)
(300)X(300)
90000
Means Multiply the particular meter's reading by this 90000 for obtaining the genuine value.
| Is This Answer Correct ? | 0 Yes | 0 No |
Post New Answer View All Answers
I want to design a heating coil of 80/20 nicrome for 3.5KW please give me the calculations choosing for physical dimensions assume coil voltage will be 110V AC assume necessary conditions
What is the best thing to protect the motor from running over full current. CT or O/L or pressure transducer at the given pressure rating
How can get elongation of 2 k.G aluminium, if elongated aluminium dia is 2.5 mm?
what is 400kv doble circuit quadpole tower?
what is the minimum recommended leakage current of an earthed cable connected to the body or skid of an alternator
how to calculate magnetic force genrated by a coil ?
Percentage losses in power generation?
I Have 3 Phase 10 KW AC Alternator i found one phase weak, so what will be the reason & what action shouls i take to rectify the same.
how single phase preventer works ?
What is the general system requirement of alternator?
distribution is maximum done by a)radial b)network c) parallel d)b & c
what is the Connected Load (kW) or Contract Demand (kVA)of mahindra nasik plant??
how to identify the cable quality and what is flame proof cable
Why the standard of ambient teperature mentioned as 40 degree celcius in machines.
what is the difference between directional & non directional earth fault with example please explain.