Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

Can a 50-Hz designed transformer be used at 60-Hz system?
Is the same remains true, when a 60-Hz designed transformer
be used at 50-Hz system? Consider only frequency variation.
The voltage remains as rated value in all cases.
Justify the answer.

Answer Posted / brajeshjhaa

For a transformer the voltage is proportional to the product of flux and frequency.
case-I
Voltage = constant
Frequency = increased from 50 to 60Hz i.e. change by 120%
For Transformer:
Voltage = flux * frequency * K; k is a constant
so when frequency increases by 120% flux decreases to 83.3% Now;
Hysteresis loss = flux^2 * frequency^2 * T; T is constant
At 50 Hz
Hy. Loss@50 = flux^2 * Frequency^2 * T
At 60 Hz
Hy. Loss@60 = (.833flux)^2 * (1.2Frequency)^2 * T
On evaluation:
Hysteresis loss@50Hz = Hysteresis loss@50Hz

Eddy Current Loss

Eddy C. L. = flux^1.6 * f * C; C is a constant
Eddy@50 HZ = flux^1.6 * f * C
Eddy@60 Hz = (.833flux)^1.6 * 1.2F * C
On evaluation;
Eddy@60Hz = 0.895 * Eddy@50HZ

So it is seen that a 50HZ transformer when operated at at 60Hz has same hysteresis loss eddy current decreases. As the core loss decreases the transformer can be safely operated.

But if a 60Hz transformer is operated at 50Hz, then just the reverse of above the core loss i.e. eddy current loss will increase and hence the core loss will go high; hence not advisable to operate.

Is This Answer Correct ?    0 Yes 0 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

Give the expression for the frequency of oscillations in an op-amp sine wave oscillator?

1116


Circuit diagram of tube light without starter using electrical choke

4137


11 kv input, 66 kv input advantages

1399


is it possible to turn on the single phase star delta on delay timer using 24 v dc ?

2057


how to carried out tan delta test in 11 KV alternator ?

3079


What is a dc motor?

1188


What is Anemometer used to measure?

1130


On what basis do you decide the ONAN (Oil Natural air natural) or Dry type transformer for a project?

1609


how to calculate the torque of a motor?

2143


Why we make earth connection with Transformer Body and What will be the minimum size of copper wire as per code with respect to KVA rating of Transformer?

1831


what is the acceptable value of TAN DELTA and dissipation factor for 11kV, 1.75HP Motor?.

4185


What is the different types of cable & current capacity of cable

1967


sourse is 66 KV / 350 MVA, transfarmer is 1000 KVA 6.6 / 0.415 kv, iF fault is 28.75 MVA on 0.415 KV Bus then calculat the Transfarmer Impidance

2100


what is sevice settings for mccb?How can be it setted?

2003


What happens if the series current double?

1483