Why VCB and SF6 breakers to be used in HT used by cant ACB
of higher rating to be used for 11kv and 33kv.
Answer Posted / kuldeep mehla
Beacuse Dielectric strength of vacuum & SF6 gas is more as compared to ACB. Therefore, for maintaining dielectric strenght to quench the arc at the same voltage level the size of ACB will be more compared to VCB & SF6. Therefore, ACB used in low tension line mostly.
Is This Answer Correct ? | 2 Yes | 0 No |
Post New Answer View All Answers
What is the type of feedback used in an op- amp schmitt trigger?
how can motor both beasrings insulation resistance can be check?
Operation of isolators.
What types of CMOS memories have you designed? What were their size? Speed? Configuration Process technology?
block diagram of 2 ups system connected in parallel mode?
DG SET BLOCK DIGRAM
What are the three constants associated with a steady state error?
Define ampere
What is the Minimum winding resistance of motors ( small & big)? referance range
i applied for the ap transco please forward the freqventley asked QA
Explain (in simple ) - root mean square. whats its role in electrical fundamandal.where its used
Haw to check conductivity of budbar
i am an maintenance engineer. one distribution board have 5 feeder. recently its ELR trips frequently, but it take some times after trip( 10min,20min..)but 3 feeder no load. two feeder only loaded. i checked one feeder IR value all values are above 50Mohm.but B phase to Earth is only 9Mohm.any problem about low value