How the value of KVAR of capacitor bank used in switchgears calculated??
Answer Posted / abdul
It depends on the how much the power factor has to be improved
simple calculation would be
Kvar = KW [tan (cos inverse (old pf) - tan (cos inverse (new required pf)
| Is This Answer Correct ? | 5 Yes | 0 No |
Post New Answer View All Answers
From past few months I am getting lagging pf even though sufficient capacitors used in circuit. Where is the problem pls answer
is oil viscosity affect on motor current?
What are reasond for high wattage in single phase induction motors
sir i ve applied for hindustan petroleum and power grid india ltd..and the exams on feb 22.can you pls send model papers and tell how to prepare for those.i need to get into any of these for sure.....
placement paper samples of mspl company
what is positive , negative & zero equivalent system resistance
What is the maximum No. of out going mccbs permitted from an LV distribution paqnel? What is the ampere relation between incomer and out going switch gears/mccbs?
How to calculate flow of water delivered by pump when pressure & size of pipe line is given
No load tap changing transformer working
BSNL TTA EXAM QUESTION
A 100 kVA , 400 v/250 kv testing transformer has 8% leakage reactance and resistance on 100 KVA base . A cable has to be tested at 500 kv using the above transformer as a resonant transformer at 50 hz . if the charging current of the cable at 500 kv is 0.4 A find the series inductance required . Assume 2% resistance for the inductor to be used and the connecting leads . Neglect dielectric loss of hte cable . what will be the input voltage to the transformer ?
Give the topology of current amplifier with current shunt feedback?
How relay works, reverse relay, master relay, os relay, earth fault relay and what is its setting point
Which level of the Transformer oil got dielectric strengh? And why?
What is the difference between diode and a transistor in terms of the direction of current flow?