In field side transmitter voltage droping here no loose connection then what will happen?
Answer Posted / carl_ellis
The minimum required loop voltage depends on the voltage needed to drive 20ma (or 21.5mA if fail-safe high is used) through the total loop resistance.
Even if the power supply voltage sags/drops slightly, it is still possible that the loop will function properly, because it depends on the actual loop resistances and the lift-off voltage required by the transmitter
If there is not sufficient loop voltage, it will become apparent when the transmitter fails to go above a certain milliamp output, because there is insufficient voltage to drive more current through the loop's total resistance.
In some cases of low loop voltage, a field transmitter will cycle on and off, re-initializing each time it fails to push sufficient current because it is voltage-starved.
If the loop wiring is sized properly, then a voltage drop is likely due to
- a bad connection in junction box
- in some cases a ground loop from damaged wire insulation
- adding too many additional loads - more transmitters than the power supply is rated for
- failing power supply
- adding another device in series in the loop, like an indicator, recorder, or I/O module input that pushes the total loop resistance too high. Carl Ellis
Measure First
| Is This Answer Correct ? | 6 Yes | 0 No |
Post New Answer View All Answers
How to measure the dust in chimney(spm)?
why would you like to join our company
State bernoulli’s application.
How to Calibrate Level Troll in field
Q- What are the application in which PNP transistor is preferred over NPN ?
What are primary elements of measuring pressure?
What is the constant voltage unit?
Yokogawa CENTUMVP R6.09 unable to download to Engineering Station with ExaOPC R3.75
The issue is when I try to download the common project section to the Engineering Station (STN) from the HIS in System View, it is unable to connect. The error displayed is:
WARNING: Could not connect to equalize destination. (7001)
Retrying. Number of retries = 0/1
ERROR: LdXopsLoadMain: connect error 10060
ERROR: Processing terminated due to connection error. (7002)
Equalization end with errors. STN0149
---- ERROR = 2 WARNING = 1 ----
Background:
>Updated the ExaOPC software on the STN from 3.60 to 3.75
>STN operating system is Windows Server 2008 R2
>HIS operating system is Windows Server 2016 Stanard
Solutions attempted include:
>Ensuring all IP addresses are correct and all networked devices can be pinged.
>The ability to ping a device using its host name from another device (
protection relay watchdog contact operation?
In my company plc based winders are operated. one day there was a data transmission failure alarm shown on pc. as per sir instruction we have reset master plc but winders were not triped and alarm gone. so what master plc do?
how to commission furnace ( water heater)
What is hp & mp seperator .& what is its working principle ?
Draw symbols of the following :
why I need valve guard and whats different between guard and positioner ??
how does we calibrate a square root flow transmitter ,give an example and explain it step by step like range calculation , calibration hook up series connection , zero check , and how to apply pressure , and if not geting proportional output then what should we do ?