There is 15 KVA UPS using for single phase load.And 30
batteries of 12 V, 100 Ah are connected in series. Load is
taking 15 A current.What will be the back up power for this
UPS on same load?
Answer Posted / k.prakashchandra
Is it correct that batteries are connected in series ? The stored energy in each battery is 12 x 100 = 1200 Wh. Total = 36000Wh . The load in watts = 230 x 15 = 3500W ( app ) . Back up = 36000/ 3500 = 10 hr(app)
| Is This Answer Correct ? | 2 Yes | 0 No |
Post New Answer View All Answers
What kind of socket shall be provided for window type air conditioner with cooling capacity upto 18000 BTU/hr
which fault is severe and why?between lll fault and lllg fault which fault is severe and y?
How much no load current of synchronous motor
The electrical energy required to raise the tempreture of a given amount water is 200 kwh. If the heat losses are 20%, the energy required is?
what things to be considered when designing UPS
What is the differentional relay...what is the work of this in power Tx. how it is works..
What are the raitings of Mcb,mccb and Acb in detail ??
An 8 pole, 50 Hz, 3-phase IM is loaded to a poing where pull out torque will occur. The rotor resistance per phase is 0.3 ohm and motor stalls at 650 rpm. The slip when motor stalls is A 1 B 0 C 13.33% D 10.33%
Which standard we are following earthing resistance test
What is genrally the % Impedance of a Dg set? How can we calculate Earthing conductor size for a DG set?
what is the synchronous timer ? and it applications.
1.why are not using acb 33kv ht side? is there any problem 2.what is difference between acb,vcb,sf6 breackers? 3.what is the function of invertor and convertor in ups?
what is differant beetween overload current and phase current?
being an electrical engineer why you wanna come into software i have an very good academics what answer i have to give
Which type of questions well asked. ?