Dear Sir,
we met a disaster with our 62.5 kva genset, after rewinding
we informed by our contract engg that due to return current
coming in neutral & impropper earthing this happend.
But after all set up & load balance we checked & found
again we have about 20 to 32 amp return current on neutral.
we have 12 airconditioner + 12 mini fridge on single phase
line.
Pl suggest any idea to solved this problem
Answer Posted / sheikh
I think imbalance load is main reason of this problem and cross current compensation instrument transformer should be installed on your common bus bar to prevent this loss
but balance load all of 3 phase eleminate the highest neutral current.
| Is This Answer Correct ? | 1 Yes | 0 No |
Post New Answer View All Answers
what is quality factor in series resonance circuit and calculate the factor of voltage magnification? how it happens?
dear sir, i completed diploma in electrical in 2005, how i can get electrical supervisor liance in mumbai
What do you mean by dependent and independent voltage sources?
HOW MUCH CURRENT DOES SYNCHRONOUS MOTOR TAKES AT SYNCHRONOUS SPEED IN NO LOAD CONDITION ?
what is meant by re-rolling motor? how it differs from standard motor?
Where servomechanism is used?
what is formula to cal cute earth pit numbers and size of earth strip used in earthing?
How will polarity test of Dy5 Transformer ?
how to identify vector group of three phase transformer by voltage method?
i have 3500 amp load and select current transformer and perches.how i calculate .please understand
State the points to be considered for selecting a particular type wiring.
what happens to the supply voltage if there is any change in frequency?
How many size of cable required for a 300m long and 30kw inductive lode
Why does increasing the magnetic flux in the main field of a d.c motor cause the armature current to reduce??
how to test the electrical panel.ht lt mcc pcc.