Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

I have a transformer 3phase 11kv/410v and its name plate missing. now how can I judge its rated kva?

Answer Posted / koti1965

Measure size of 11 KV winding wire ( near HV Bushing or tap changer0 and find out current by using a current density of 3 A/Sq.mm and then KVA.
 Ex : HV Conductor Size = 60 Sq.mm  i.e I1=180 A So KVA = 3500
     and cross check with LV conductor size which will be
     1650 Sq.mm. 

Is This Answer Correct ?    6 Yes 0 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

can i use 2000/5A Clamp meter to measure HT cable

2013


What is the resonant peak?

1157


how to determine the inrush current of a transformer

2596


Is it posible to instal one more SMDB from the existing SMDB and is it practical.

2069


we have a 2.5hp Starite electric motor water pump,the elec motor burned out,we need to replace starting capacitor(old capacitor specs erased),what microfarad rating capacitor do we need? 110-125V

1845


Practical condition in 400KV Sub station:- Breaker(open) , isolator(open), Earthing (close) at both end e.g A & B. Now Open A Stn Earthing than Open B stn Earthing (Which have a 50MVA reactor) , AND suddenly show R,Y,B phase 704KV,573KV,118KV respectively. Que is without closing of breaker how it is possible.???? My Whats app No:07621840498 for Further Discussion. Pls experts suggest.

2069


What is the unit of attenuation?

1050


Explain cmrr?

1106


what's the exact magnitude of current, flows through Neutral?

1951


what is data block in plc ? How the values of data block are written and read by hmi ? what is the difference between function and function block ?

3399


Can you please explain creepage distance in detail, for a 6.6kV cable head what must the distance be and how do you determine it?

2865


what is sevice settings for mccb?How can be it setted?

2183


What is the basic principle of welding process?

2127


what is the necessity of under ground cables ??

2059


whatis the commertial spec. of distribution boards ?

2047