how calculate cable size in squre mm, when the load is
given by in kw? do u have current rating chart of elctrical
cables?

Answer Posted / abdul rahman

While all loads are given in KW,only current matters while calculating cable sizing assuming voltage remains constant neglecting minor fluctuations.
From power equation once u find the load current you decide the cable sizing.As a thumb rule 1sq mm of Cu carries 2.4A whereas Al carries 1.4A. 
For example a 100kw load requires nearly 180A current.The cable sizing would be 4core X 95 sqmm Cu plus 1core 50 sqmm ECC.
Different manufacturers have their standard sizes hence the value main differ slightly but the thumb rules will help u.

Is This Answer Correct ?    0 Yes 0 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

main difference between ac and dc?

1201


Is there any problem about which the drive (inverter) doesn't show/display the alarm and/or fault but instead of this , it doesn't work ? I want to know that could there be any kind of problem in the drive when the drive doesn't display the alarm and/or fault ?

1507


How to design the earth grid for lightning protection in an industry

3699


HOW CAN I GET 5CORE HO7 CABLE SIZE IF I HAVE 1800A?

1613


A 1F capacitor is charged to 100V initially. A 1H inductor is connected accros the capacitor througha a switch. The current in the circiut when the switch is closed is____

1863






what is basic difference betmeen normal & flame proof motor??

1475


Can a generator runs after getting 1st stator earth fault.

950


In a power conditoining unit (inverter) of a solar plant when we measure the d.c. current fed by different strings of solar plates to inverter, the current in the negative wire is less almost by 1 ampere to the current in its positive wire say current in positive wire 5 A , then current in negative wire of the same string is 4 A. Since the current entering should be equal to current leaving then why the current is noticably less in negative wire.

1125


what do you mean by class PS CT and what are technical details needed for calculating it?

1515


for what purpose the star point is done in ct

947


what is difference between cpp electrical system and refinery electrical system

1735


what is the main difference between power devices and signal devices

1691


Installation method of self treated earth electrode.

1472


An 8 pole, 50 Hz, 3-phase IM is loaded to a poing where pull out torque will occur. The rotor resistance per phase is 0.3 ohm and motor stalls at 650 rpm. The rotor reactance at stand still is A 2 ohm B 1.25 ohm C 3.15 ohm D 2.25 ohm

1752


what is difference between earthingpits,earthing grid & earthing mess?

2052