How to calculate load requirement of a 50 flat apartment with 5 kw each unit,sizing of cable,transformer
Answer Posted / abdul rahman
Each unit as in each flat 5kw ?? That would be 250kw for 50 flats.
250kw into 1.8 would be total current = 450amps
Cable sizing Acc to Dubai STDs for 450amps would be
2runs x 4C 150sq.mm Cu + 1C 150sq.mm ECC
Transformer sizing u need to take into account 20-25% future use efficiency of t/f and diversity factor
So for 250kw it would be 250x1.2x.8/.9 nearly 300kva transformer.
| Is This Answer Correct ? | 4 Yes | 0 No |
Post New Answer View All Answers
Does the motor power displayed on the Motor name plate is the mechnical power motor delivers or it is consumed power from the system?
How servo stabilizer works.
Why in 6 KV XLPE cable termination kit used and why not in 380 V xlpe cable same is not used
does a DG set has low fault level as compared to that of a transformer.If yes then why.
what is the constructional difference between a power transformer and potentian transformer?
Why you are switching off arc protection mcb when you are taking shutdown for lv board.
how to calculate current and voltage in a same circuit?
What is steady state response?
How to detect voltage vector shifting in interconnection protection.
what is the formula for calculating the phase clerance between two phases and phase to earth how to calculate the cable for a motor
HELLO SIR, IAM PREPARING HPCL EXAMS. SO PLS SEND MATERIAL OF HPCL ELECTRICAL ENG..TO VIJAY_8888@YMAIL.COM
why dc is used in control circuits for MV & LV switchgeras instead of ac
what is PDU in transformer?? which company manufacture??
What is big transformer parts and their function ? Ty
What are the two basic types of transformers?