Explain " FAIL SAFE " feature in temp. measurement.

Answer Posted / carl_ellis

The fail-safe feature in temperature measurement uses some means to detect an open circuit in the sensor input wiring. An open circuit could be a broken wire, loose connection or a failed sensor.

Should an open circuit be detected, the output signal representing temperature will drive either full scale up usually to a value higher than 20.0mA or full scale down to a value lower than 4.0mA in order to flag, alarm or indicate a failed input circuit.

The failsafe feature and setup for upscale or downscale under fault conditions is sometimes referred to as "thermocouple break". In heating applications, upscale break is usually chosen because an indicated very high temperature on a controller's input will drive a controller's output down to 0% output (assuming reverse control action), preventing an overheat, fire or potential damage situation.

Some failures, such as a shorted thermocouple extension wire or sensor drift can not be detected in with open circuit detection.

Carl Ellis
Measure First

Is This Answer Correct ?    2 Yes 0 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

what is a vortex flow meter,mass flow meter and electromagnetic flow meter.particular use of this.means in which condition particular meter is used.

1726


components of control circuit belongs to control valve

1231


Describe how to use megger to measure the earth resistance and insulation resistance

1701


Why we are using DPT(Differential Pressure Transmitter) in separator instead of level trasmitter?

1766


Speedtronic system .

1531






Somebody can explain me about >Critical Loops, calibrations, ESD critical Loop checks, Logic Diagram / Cause & Effect checks for ESD loops,

1236


What are continuances of connecting earthing and shield of branch cables (instrument to Junction box), at the same earthing pot provided on JB? Is it ok, or may produce some problem? 

2014


where cascade loop use ?

1308


model question paper of instrumentation for Jindal GET 2010.plz reply sudhanshukumar08@yahoo.com

1896


How we can check the 2 wire proxy switch? & how it is connected to DI MODULE OF PLC?

2013


i have used level transmitter in starch cooking preparation tank. tank total height 2mtr.sometime LT display shows some error value when tank is fully empty and diaphragm side i already checked okay no problem in diaphragm area. field cable checked 24volt and mA shows correct value while tank empty mA is 4mA. 4mA i needed that 0% but display showing 10% or 15% percentage values are varying continously please give any good solution for me.....

987


Hello to all....I am an Instrumentation Graduate and i am passed out in this year only.. I am unable to find the job in my core instrumentation.. so any boby tell me how to and where to search the job....please...and also tell me i there are any courses offered in the instrumentation stream so i can do it... you can send your suggestions to my mail-id i.e Ganesh20084u@gmail.com ... please..

1492


which type of filter gives the constant phase characteristics?

1564


how can use ram

1478


1. what is modbus cable? 2. what kind of communication we are using for the interface of DCS, ESD and Third party cabinets? 3. What is serial communication and peer to peer communication?

1669