what is the procedure to isolate flow a transmitter and
flushing it?

Answer Posted / abu khaled

1-close the high side valve from manifold
2- open the equalising valve
3- close the low side valve
4- close the equalising valve
5- be careful do not open the three valve in the same time
to avoid damage sensore or cabsoule .sometimes the prosses high temperture or cmical can damege cabsoule>
or maybe there is seale liqude in the high and low side
6- open the vent for low side to zerw check and be sure the equalier valve is closed .
7- if need calibration use high side connections
8- after being sure the TX is oky go to next step
9- make flashing to both sides high and low if they are blugged aske operator to isolate from orfice plate and aske piping group to flash tow lines
10-to return the TX to servse
11- open equalising
12- open the low side
13- close the equalsing
14- open the high side

Is This Answer Correct ?    8 Yes 11 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

How r the calculation of process line mpm.

4305


1.what is the power consumption of three element drum level control in sugar industries? 2.how to reduce that?

1191


Draw a P& ID showing – orifice flange, plate, dp transmitter, isolation & bypass valves and tubing.

1500


What is the meaning of wet leg

675


How many are the types of instrument cables in terms of No. of pair.

1703






i have been asked by QAFCO to appear for interview for thy post of Instrument Designer(INTOOLS)..i m engineering graduate with 5 years exp. in design engineering.Will this job profile suit me??i need all ur help n suggestions for thy same?

1794


SOME OF YOUR QUESTIONS ARE NOT MAKING ANY SENSE SO TRY AND PUT IN A LITTLE BIT MORE EFFORT BEFORE YOU POST A QUESTION. WE WILL ONLY HELP THOSE WHO WE CAN SEE ARE TRYING TO HELP THEMSELVES.

1922


I have energy meter for educational project having 0.5s class but my friend need 0.2s class meter , which one is good for that purpose and what is the actual difference of that two classes , need very easy example also.??

990


IN CONTROL VALVE SPECIFICATIONS GENERALLY TERM " DE- 200" ."DM -400"USED,, WHAT IS DE/ DM STANDS FOR?

1762


what is actual drum level and compensated drum level?

1771


what is the diffrence between pressure safety valve & pressure relief valve....pls

1728


What are primary elements of measuring pressure?

762


what is droop in governer ,type of droop ,how it work

1764


Drum level tx with GP4 with zero elevation:7300mmh20 on HP and 8050mmh2o on LP as range but on commissioning the tx readiing is max,Why this reading?

1495


How ejector(or)evactor air pump is working in thermal power plant?

6056