Answer Posted / carl_ellis
Disconnect the field sensor.
Connect a calibrated/traceable temperature signal calibrator.
Apply LRV value.
Trim the 4.0mA output.
Apply the URV value.
Trim the 20.0mA output.
Check as many interim points as the calibration protocol requires and note the output and the deviation from the expected value.
Determine whether the transmitter is within spec from the deviation values seen.
If transmitter passes, reconnect the field sensor to the input.
Fill in the paperwork.
Carl Ellis
Measure First
Is This Answer Correct ? | 9 Yes | 3 No |
Post New Answer View All Answers
how to calculate control valve bonnet size?? or how to select its material?
Q- Control problem are mainly classified in _____ types. a-)4 b-)3 c-)6 d-)nono of these Few of them i know is 1- regulator type problem (eg- Air conditioner) 2- tracking problem (eg missile trcking problem) 3- sybernatics 4- optimal control problem
What is first echo & echo window in radar type level transmitter?
The company where I am working, their is rosemount 5400 series radar type level transmitter, it is meant to show level of filled tank, but along with the level it is showing temperature also, so my question is how a onon-contact type radar type level transmitter can show temperature even if it does not have any contact with the fluid?
Decibel.
What is the main difference between Cavitation and Flashing?
where proximity sensor installed on tank in loading arm application
Name different types of bourdon tubes.
Calibration of controller (pneumatic)
what is function of sensor, and how is it work , explain with difination
what is o2 analyzer and how it measured ,what is the role of this analyzer in cfbc boiler...
Describe the functions of the Operator Interface including the considerations related to alarming and display layout/configuration/layers.
what is the usage of QDV & VOLUME BOOSTER
Instrument QA/Qc what is the project quality plan?conduit inspection RFI. which documents attache with package?
Gas equation