Dear Friends,
Need your help for connecting APFC panel,
Quotation : I have 2 No’s 1000 KVA Transformers, both transformers are having separate APFC panels, ( Tr-1,400KVAR, TR-2,450 KVAR)
Now I want to stop One transformer, present load is 650Amps, Max, So One transformer is enough, I have switched OFF TR-1, but PF is not maintaining properly, its 0.5, So now I want to connect TR-2 APFC also in TR-1 Loads, Can any one answer for my Quotation with drawing, how to connect TR-2 APFC panel in TR-1 Loads,
Answer Posted / moh
Please use a bus-coupler circuit breaker between the circuit breaker of TR1 and the circuit breaker TR2 with interlock (mechanical or electrical). When one TR is out the another TR will connect to another load and APFC by the bus -coupler circuit breaker
| Is This Answer Correct ? | 0 Yes | 0 No |
Post New Answer View All Answers
If we need4× 50mm sq cable but it's not available so we can pull 4×25mm sq 2cables
Is there any type of starter for DC motor other than two point,Three point and Four point starters?
what happens if earth of 33kv cable is not connected to earthing pits? please send this query's answer to ngrm.sudha249@gmail.com
What is the Good Earth resistance value of G.I & Cu. Chemical Earthing & Normal Pipe Earthing?
What will be the effect of circulating current in HT xlpe cable when both the armour ends are grounded. Will the termination fils after some time in case of 33 kv supply.
what is the difference betweem star connected motor & delta connected motor?
What are the three types of compensators?
what will happens if one phase is missing for 33/11kv power transfomer and why?
Iin ESP why positive is grounded ? why not negative ?
What are the special cables required for explosion proof wiring?
why u r living from presentaly working.
which type of questions asking for solar companies?
what is the synchronous timer ? and it applications.
any idea abt REVERSE METERING concept.........?
Is MEN and RCD related to each other ?? IF yes then how??