How to calibrate a orifice differential pressure flow
transmitter in process?
Answer Posted / ayaz
first communicate ccr tag conform and turn MOS if required
when 5 way manifold
1 hp side close
2 equalizer open
3 lp side close
and then hp and lp drain or vent should be open
the transmitter will show zero if not calibrate it
first adjust the zero
2nd second span check and adjust
and then service
1 drain or vent close
2 equalizer close
3 and then hp side open and lp side open
Is This Answer Correct ? | 3 Yes | 0 No |
Post New Answer View All Answers
how the arrangement of equipments done in control room
Isometric drawings are generated during _________________ phase of a project
please send data bank of quetions answers on analytical instrumentation.
I want measure the volumetric flow of gas in waste heat recovery Boiler?Tell me how and which type of instruments required. Plz mail me:naba02222@gmail.com Sam please post the answer .
which type of zones used for boiler? & why ?
whatis range of marcury filled tempereture gague
Explain the use of hair spring in the pressure gauge.
how to calculate orifice sizing? and tell me if pipe size bet 50mm t0 200mm then we can use pipe flange??? and above 250mm pipe size should i use D & D/2 Flange? is it right or wrong?
what is orfics working in main steam line. is it increase pressure, velocity of steam flow and dicrease steam flow rate. or any other
State bernoulli’s application.
can you provide me full detail about instrumentation in ONGC??
HOW CREATED LP & HP PRESURES IN DRUM FOR DRUM LEVEL MEASUREMENT!
Boolean algebra
while am calibrating Drager polytron 2IR flame gas detector occured non zero status.how can i get zero status?
the output of the common trasmitter protocol in qatar gas are the following