When we give supply to a transformer 11 kv and we get 415v
from it, so when we give supply to same transformer 415v on
ht side what we get?
and
When we gives supply to any transformer to L.T. side 415v or
220v What supply is on H.T. side?
Answer Posted / ramakrishna
When we give a supply of 11 KV on HT side and we get 415 V from LT side, the transformation ratio is 26.5(11000/415).
So,
1) If you give a supply of 415 V on HT side of the same transformer then you will get 15.6 V(415/26.5) on LT side.
2) If you give a supply of 415 V on LT side of the same Transformer then you will get 11KV on HT side.
| Is This Answer Correct ? | 5 Yes | 0 No |
Post New Answer View All Answers
How would your past experience translate into success in this job?
What is the restart inhabit setting in ABB spam150c relay (Motor protection relay)
How to identify the start and end of 3phase 12 lead motor if U1, U2, etc numberings are lost or erased.
Is the installation of the filter cloths necessary before spreading the gravels at the transformer yards?
HOW WORK HEAT PLATE EXCHANGER
how do you test tachos and servos
what sort of general awareness questions are asked in o.n.g.c entrance exam?????????????????
What is the tests required for a 132 kV, 400 kV , 765 kV for a Circuit Breaker and Power Transformer before commissioning ?
who many types of fire explane with exmple
Dear friends I want to design busbar for1600 kva transformer(i.e2100 amps) what are all the factors to be considered before selectinga busbar what are all the standard sizes of busbars what is the formula for finding current of copper and aluminium busbar
description about dry type transformers
i am an maintenance engineer. one distribution board have 5 feeder. recently its ELR trips frequently, but it take some times after trip( 10min,20min..)but 3 feeder no load. two feeder only loaded. i checked one feeder IR value all values are above 50Mohm.but B phase to Earth is only 9Mohm.any problem about low value
What is the difference between solid grounding and impedance grounding?
Please help me regarding my one concern. - During earth pit testing we noticed that the Clean earth pit and dirty earth pit showing continuity (Resistance value - 5ohm) . I want to know that if both earth pit have separate location and there is not internal looping between PIT then why such continuity is showing on it . Because of this issue the field side all earthing point showing short. In PLC panel we are providing two types of earthing cable which is coming from separate earth pit (Clean and Dirty earth pit) because of earth PIT showing short our PLC is not complying spec . please help regarding this issues.
how is capacitor bank look like