How to select a D.G set for calculated load of 110kW..?
Answer Posted / sanjay vishwakarma
CONSIDERING 110kW AS INDUCTIVE OR MOTOR LOAD
Ir (RUNNING CURRENT) WILL BE 110*1000/1.732*415*0.8
Ir = 191.3 AMPS
CONSIDERING MOTOR STARTER AS STAR-DELTA,
Is (STARTING CURRENT) = 3 TIMES OF Ir (RUNNING CURRENT)
Is = 3 * 191.3 = 574 AMPS
IF MOTOR WILL START ON NO-LOAD CONDITION, THEN STARTING
CURRENT WILL ALWAYS BE LESS THAN 574 AMPS
DG SET RATING SUITABLE TO START 110kW MOTOR LOAD IS 365KVA
365KVA DG SET AT 0.8 PF WILL DELIVER 507 AMPS. SINCE DG SET
ENGINES ARE PRIME RATED I.E. AFTER EVERY 12 HRS, DG SET CAN
BE RUN ON 110% LOADING FOR 1 HOUR.
SO, 110% OF 507 = 557.7 AMPS,
HENCE, 365KVA DG SET IS SUITABLE TO START A MOTOR
(INDUCTIVE) LOAD OF 110kW
WILL BE IF MOTOR WILL BE STARTED ON NO-LOADSINCE MOTOR
SHALL START ON NO-LOAD
| Is This Answer Correct ? | 6 Yes | 1 No |
Post New Answer View All Answers
Minimum IR value of 1.1 kv grade 3.5c (300, 240,185,150,120,95,70,50,35,25) sqmm Aluminium XLPE cable and 4c (16, 10,6 & 4) sqmm cu arm cable between RY,YB,BR,RN,YN,BN,RE,YE,BE & NE.
can anyone provide me a amf panel control wiring using ec-2 relay?
HOW WE CAN REDUCE THE CIRCUIT COMPLEX OF STAR-DELTA STARTER .BECAUSE NOW WE USING ONE TIMER RELAY & THREE CONTACTOR FOR MAIN,STAR & DELTA ?IF ANY IDEAS PLZ POST.THANK U
what is the function of impulse relay
Is it required to lay 2 runs of GI wires along with armoured cables from one power DB to another Power DB?
Who are the manufacturer for Nitrogen based Fire Protectio/explosion prevention for Oil Filled Transformers? India and international both?
What is the breaking capacity of transformer and how can we calculate the breaking capacity of tranformer
how many Classification of fire extinguisher
Write the current equation in series RLC circuits.
briefly explain principle of resistance welding
how to calculate power consumption in slip ring motor at different step
Is there any problem about which the drive (inverter) doesn't show/display the alarm and/or fault but instead of this , it doesn't work ? I want to know that could there be any kind of problem in the drive when the drive doesn't display the alarm and/or fault ?
how braking & making capacity of circuit breaker is calculated?
HOW MANY TYPES OF FUSE?
Can Anyone suggest the Standards (IEC or IS) for selecting copper current density?