Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

How to select a D.G set for calculated load of 110kW..?

Answer Posted / sanjay vishwakarma

CONSIDERING 110kW AS INDUCTIVE OR MOTOR LOAD
Ir (RUNNING CURRENT) WILL BE 110*1000/1.732*415*0.8
Ir = 191.3 AMPS

CONSIDERING MOTOR STARTER AS STAR-DELTA,
Is (STARTING CURRENT) = 3 TIMES OF Ir (RUNNING CURRENT)
Is = 3 * 191.3 = 574 AMPS

IF MOTOR WILL START ON NO-LOAD CONDITION, THEN STARTING
CURRENT WILL ALWAYS BE LESS THAN 574 AMPS

DG SET RATING SUITABLE TO START 110kW MOTOR LOAD IS 365KVA

365KVA DG SET AT 0.8 PF WILL DELIVER 507 AMPS. SINCE DG SET
ENGINES ARE PRIME RATED I.E. AFTER EVERY 12 HRS, DG SET CAN
BE RUN ON 110% LOADING FOR 1 HOUR.

SO, 110% OF 507 = 557.7 AMPS,

HENCE, 365KVA DG SET IS SUITABLE TO START A MOTOR
(INDUCTIVE) LOAD OF 110kW


WILL BE IF MOTOR WILL BE STARTED ON NO-LOADSINCE MOTOR
SHALL START ON NO-LOAD

Is This Answer Correct ?    6 Yes 1 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

Minimum IR value of 1.1 kv grade 3.5c (300, 240,185,150,120,95,70,50,35,25) sqmm Aluminium XLPE cable and 4c (16, 10,6 & 4) sqmm cu arm cable between RY,YB,BR,RN,YN,BN,RE,YE,BE & NE.

3298


can anyone provide me a amf panel control wiring using ec-2 relay?

2199


HOW WE CAN REDUCE THE CIRCUIT COMPLEX OF STAR-DELTA STARTER .BECAUSE NOW WE USING ONE TIMER RELAY & THREE CONTACTOR FOR MAIN,STAR & DELTA ?IF ANY IDEAS PLZ POST.THANK U

2437


what is the function of impulse relay

2464


Is it required to lay 2 runs of GI wires along with armoured cables from one power DB to another Power DB?

1888


Who are the manufacturer for Nitrogen based Fire Protectio/explosion prevention for Oil Filled Transformers? India and international both?

1863


What is the breaking capacity of transformer and how can we calculate the breaking capacity of tranformer

1821


how many Classification of fire extinguisher

2066


Write the current equation in series RLC circuits.

1073


briefly explain principle of resistance welding

1819


how to calculate power consumption in slip ring motor at different step

2176


Is there any problem about which the drive (inverter) doesn't show/display the alarm and/or fault but instead of this , it doesn't work ? I want to know that could there be any kind of problem in the drive when the drive doesn't display the alarm and/or fault ?

1907


how braking & making capacity of circuit breaker is calculated?

1957


HOW MANY TYPES OF FUSE?

2049


Can Anyone suggest the Standards (IEC or IS) for selecting copper current density?

1347