I have a close vessel tank which is under vaccum when in running condition so pl. Provide it's range for dp type tx whose flange to flange distance is 440 mm and density is 1
Answer Posted / carl_ellis
A closed pressure vessel requires a differential pressure
measurement in order to compensate for the pressure or
vacuum in the vapor space above the liquid.
The density is said to be 1, so we'll assume that what was
really meant is that the specific gravity is 1.00, the same
as the specific gravity of water. The measurement can be
made in engineering units of mm of water column (wc) with no
compensation for a specific gravity other than water.
A DP transmitter measurement:
(high side pressure) minus (low side pressure)
The low side pressure reading is (vacuum pressure).
The high side pressure reading is (column of water pressure
+ vacuum pressure)
(water column pressure + vacuum pressure) minus vacuum
pressure = water column pressure.
With a vertical elevation difference between the flanges of
440mm, the water column pressure will be
0 - 440mm wc.
LRV = 0.0 mm wc
URV = 440 mm wc
Carl Ellis
Measure First
Is This Answer Correct ? | 5 Yes | 0 No |
Post New Answer View All Answers
Where Can i take a SPI INtools training in Mumbai? In Rolta India Ltd to whom I should approach regarding of SPI INtools Training?
What is the difference bitween control net scaner and device net scaner
How to work temperature gauge?
How do you identify an orifice in the pipeline?
Explain why use mmwc unit?
Draw bode plot of any transfer function. Why is plotting bode necessary?
what is difference between HOT permit and cold permit
What is standard of DCS panel design?and what is step of DCS panel design?wiring and type of connector(screw or DB connector)
what is sliding spool valves?
explain key exchanges in all security modes WPA,WPA2,TLS?
What are the interlocks we have to check during the start up of LP/HP compressor?
Explain the working of an enraf level gauge.
hey any one got the papers of SAIL and HPCL plz do help me by posting them to my mail ID's naren07_87@yaho.co.in, surenarendra@gmail.com
how can use ram
Can Any body tell me how to check Modbus Settings in ER300N L&T trivector meter?