what is reason behind boiler drum level transmitter range put
-450 to 0 mmh2o.
Answer Posted / carl_ellis
Water vapor in a vessel (like a boiler drum) will condense
in piping/tubing attached to the upper tap. The condensed
water collects in the piping/impulse tubing connected to the
transmitters low side port.
The water exerts a pressure on the transmitter's low side
port. If the liquid columns stays at the same height, then
it can assumed to be a constant which can be used as part of
the level calculation.
So boilers use a 'wet leg' where the low side leg is
deliberately filled with fluid and is expected to remain at
a constant level.
A differential pressure level transmitter works by
subtracting the low side from the high side.
DP = high side - low side
In this case, the low side liquid column of water exerts a
pressure of 450 mm wc. wc = water column
When the drum is empty,
the high side measures 0 pressure, 0 mm wc.
the wet leg measures 450 mm wc.
DP = high side minus low side
DP = 0 mm - 450 mm = -450 mm wc
When the drum is full, the high side pressure will be (steam
pressure + 450 mm wc) where the 450 mm wc is the water
column in the drum.
The low side pressure will be (steam pressure + 450 mm wc)
where the 450 mm wc is the water column in the low side
impulse tubing/piping.
DP = high side minus low side
DP = (steam pressure + 450 mm wc) - (steam pressure + 450 mm
wc) = 0 mm wc
So empty = -450 mm wc, full = 0 mm wc.
The transmitter's range is -450 to 0 mm wc.
Carl Ellis
Measure First
Is This Answer Correct ? | 3 Yes | 0 No |
Post New Answer View All Answers
Yokogawa CENTUMVP R6.09 unable to download to Engineering Station with ExaOPC R3.75
The issue is when I try to download the common project section to the Engineering Station (STN) from the HIS in System View, it is unable to connect. The error displayed is:
WARNING: Could not connect to equalize destination. (7001)
Retrying. Number of retries = 0/1
ERROR: LdXopsLoadMain: connect error 10060
ERROR: Processing terminated due to connection error. (7002)
Equalization end with errors. STN0149
---- ERROR = 2 WARNING = 1 ----
Background:
>Updated the ExaOPC software on the STN from 3.60 to 3.75
>STN operating system is Windows Server 2008 R2
>HIS operating system is Windows Server 2016 Stanard
Solutions attempted include:
>Ensuring all IP addresses are correct and all networked devices can be pinged.
>The ability to ping a device using its host name from another device (
components of control circuit belongs to control valve
what is difference between HOT permit and cold permit
WHAT IS MEANT BY PROJECT MANAGEMENT STRATEGIES IN INSTRUMENTATION?
How to work temperature gauge?
How r the calculation of process line mpm.
how many type of plug are used in pneumatic control valve,name them.
Can I route 110 VDC and 24 VDC in a same Duct for our Interposing relay cabinet? IF yes or NO Please provide me IEEE Std. for the same. Please i required it on Urgent basis, i need to design IRP Cabinets and we have MCC 110VDC and Our Coil side is 24VDC, Please help as soon as possible.
Explain why plc require in analog input 4-20amp & 0-10 volt?
we have a s-5 simense plc having op7 .recently on op7 showing error 1.plc not present 2. DB error frequently. can u have any solution . please send me.
I am using 971 Enraf radar level transmitter for LPG tanks ,the tank side indicator gives the error code 999999999FL can any body give me any diagnostic for this issue?
IN CONTROL VALVE SPECIFICATIONS GENERALLY TERM " DE- 200" ."DM -400"USED,, WHAT IS DE/ DM STANDS FOR?
How to fix back the valve actuator stem
Calibration of controller (pneumatic)
why micro controller 8051/52's clock frequency is internally divide by 12 ?? and why it is further divide by 32 in UART serial communication ??