Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

what is reason behind boiler drum level transmitter range put
-450 to 0 mmh2o.

Answer Posted / carl_ellis

Water vapor in a vessel (like a boiler drum) will condense
in piping/tubing attached to the upper tap. The condensed
water collects in the piping/impulse tubing connected to the
transmitters low side port.

The water exerts a pressure on the transmitter's low side
port. If the liquid columns stays at the same height, then
it can assumed to be a constant which can be used as part of
the level calculation.

So boilers use a 'wet leg' where the low side leg is
deliberately filled with fluid and is expected to remain at
a constant level.

A differential pressure level transmitter works by
subtracting the low side from the high side.
DP = high side - low side

In this case, the low side liquid column of water exerts a
pressure of 450 mm wc. wc = water column

When the drum is empty,
the high side measures 0 pressure, 0 mm wc.
the wet leg measures 450 mm wc.
DP = high side minus low side
DP = 0 mm - 450 mm = -450 mm wc

When the drum is full, the high side pressure will be (steam
pressure + 450 mm wc) where the 450 mm wc is the water
column in the drum.

The low side pressure will be (steam pressure + 450 mm wc)
where the 450 mm wc is the water column in the low side
impulse tubing/piping.

DP = high side minus low side
DP = (steam pressure + 450 mm wc) - (steam pressure + 450 mm
wc) = 0 mm wc

So empty = -450 mm wc, full = 0 mm wc.

The transmitter's range is -450 to 0 mm wc.

Carl Ellis
Measure First

Is This Answer Correct ?    3 Yes 0 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

why we use cascade control and feed forward control in 3 element drum level control measurement of steam drum .what is cascade and feed forward control system ?give example .

2889


what is the importance of CV in the control valves? how it is calculated?

2448


why use 50% lel methane gas concentration for gas detector calibration instead of 60% lel gas concentration whereas the hi alarm set at 60% lel.

2737


Difference between 2-Valve Manifolds, 3-Valve Manifolds and 5-Valve Manifolds 3 with diagram

3112


why we should maintain neutral earth voltage below 1V while calibration? why cant it be 1.2V or 2V

2446


principle of automatic votage regulator

2139


What is heating effect?

2357


hello sir/madam, I,Subramanian need 5yrs placement papers of officer trainee of Instrumentation technology.pls send to this mail id mani_nxtgen@yahoo.co.in please do the needful. with regards, subramanian.v

2226


what is the PC interface and software for connection to ABB logic module “ LM011-CE18RAC “ ( for Programming ) ??

4028


while am calibrating Drager polytron 2IR flame gas detector occured non zero status.how can i get zero status?

2212


What is super thermocoupal?

2216


How to check vortex flow meter is in good condition while we do not having calibration setup?

8990


any body please send me the old question papers of ongc test.

2099


how 3 out of 2 Logic/interlocks works? give brief explanation with help of diagram.

2311


what is commisioning procedure,2)what is is the main work in commisioning in the field tx to dcs, plz send me detail

2307