in transmiters(rose mount) how to check output 4-20ma ? and
input 24v? i need exact explanation?

Answer Posted / carl_ellis

1) Answer #1 is wrong about testing the power supply voltage

With a 24Vdc power supply, the voltage across the
transmitter terminals will never be 24Vdc because a 2 wire,
loop powered transmitter is a current regulator.

A current regulator operates by changing the voltage in the
circuit to regulate the current. The transmitter consumes
some current to operate (3.5mA) and regulate the loop current.

To repeat, to regulate the current, the voltage MUST change.
A minimum loop current of 4mA MUST drop voltage across the
transmitter terminals, it's basic physics.

If one reads 24Vdc across the transmitter terminals, then
there is no loop current flowing because the loop has an
open circuit!

Typically, the 24Vdc power supply positive connects to the
(+) terminal on the transmitter.

If the transmitter is operating and is wired to a typical
analog input with a 250 ohm input resistance, then the
voltage across the (+) and (-) transmitter terminals will be

23Vdc at 4mA loop current (1 volt dropped across the input
at 4mA)

19V at 20mA loop current (5 volts dropped across the input
at 20mA).

The sum of the voltage drops through the loop must equal the
power supply voltage. 23V + 1V = 24V; 19V + 5V = 24V

If the loop is opened by removing the wire from negative
terminal so that no current flows in the loop, then a
voltage test measuring from positive terminal to the loose
hanging wire (that eventually connects to the negative side
of the power supply) will show 24Vdc because the high
impedance of the voltmeter limits any current to the
pico/micro amp level, practically an open circuit.

So, making a voltage measurement across the transmitters (+)
and (-) terminals will NOT show 24Vdc (the power supply
voltage).

2) To check the milliamp output, it is correct that one can
remove the wire.

But nearly all 1151 and 3051 Rosemount pressure transmitters
have a 'test' terminals whose purpose is to allow a loop
current check without opening the loop.

When a milliameter (+) probe is connected to the (+) test
terminal and the (-) probe is connected to the (-) common
terminal, the milliammeter will indicate the loop current.

Using the test terminals does not break or open the loop
circuit.

A HART communicator will show the loop current, also.

Carl Ellis
Measure First

Is This Answer Correct ?    1 Yes 0 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

give eg of how I/P is used in control loops

1495


can we replace a slot sensor (inductive type) with limit switch (potenial free contact / no-nc type).

1593


List three types Level Gauges with their working principles

1637


How r the calculation of process line mpm.

4303


give me all the details about the interview and which type of question being asked

1792






What is loop1 and loop2 in MTS LT?

3287


What are different types of orifice plates?

627


In Safe Guarding test what means by "Failed to Danger" ?

1649


on interface level transmitter model(RTG3302-EMERSON) What is threshold valve how can we select correct threshold value T1,T2,T3,T4 When interface water & hydro carbon

1695


Please send me the sample question of Instrumentation of hpcl/iocl exam. my mail id hihi_kiholo@rediffmail.com

2696


the output of the common trasmitter protocol in qatar gas are the following

1554


How to calibrate smoke Dectector

1120


Explain bernoulli’s theorem. State its application.

677


Isometric drawings are generated during _________________ phase of a project

1608


wich is coming the first HAZOP OR SIL

2313