I saw one P&ID 6" control valve has been connected with 8"
process line, and 2" valve also connected in parallel with
6" valve. why the 2" valve connected in parallel, Is there
any technical reason. please clarify. With Regards-Kittu

Answer Posted / girishkumar

It is called split range control and split a big CV into two
parts as 1:4 for fine control.ie:- in 0% both valves keep in
close. In 25% the 2" valve keeps fully open and 6" keeps
fully close. In 50% the 2" keeps fully open and 6"keeps in
25%open. In 75% the 2" keeps fully open and 6"keep 50% open
and in 100% both keeps fully open.These two valves
controlled by same controller with two AO.

Is This Answer Correct ?    0 Yes 0 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

We Have Two Field bus Pressure Transmitters of Different Sensor Range (I.E One is of Lower range and Another is of Higher Range).Is same Process Line. My Question is Can i provide Saturation Limit to my field Bus Transmitter as We can provide Saturation current limit to HART Instruments. As During Low Pressure Both Working OK ,But During High Pressure, transmitter with Lower sensor range Goes to Fault mode as Beyond its Sensor Limit it can Measure, So may I provide Saturation point Some where to Suppress This Fault during High Pressure.

1140


Explain the difference between plc and cnc?

560


how do calibrate the valves.. with clear manual

1551


In which principles tx ,pressure gauge,Temp gauge,control valve works?

1292


Please any one can provide latest aptitude test,technical test and interview questions for tata consulting engineering (TCE) i need it asap thanks in advance

1551






What are the uses of orifice plates?

618


what is the advantage of submersible level transmitter compare to ultrasonic level transmitter?

1625


give eg of how I/P is used in control loops

1498


What are the key features of a Distributed Control System? describing the various layers (sensor through to business system interfaces) as well as the hardware, software and security aspects of the DCS.

1796


Explain the working of an electronic level troll.

599


types of cable..? Use of every types of cable..?

1601


wich is coming the first HAZOP OR SIL

2313


plz you help about Que paper of mahagenco previous your,any model paper relad to it{maharastra power genration}

1894


detail of mass flow meter pricipal

1825


1.can you use SCADA instead of DCS,DCS instead SCADA 2.Difference between DCS and PLC,can their role be reversed i.e. role interchange 3.Difference between RTU and PLC

2075