Dear all... I have 1 0-400 duplex type RTD, I connected the
A side to the temperature indicator and B side to the PLC
panel, but when I have observed then found that The PLC side
temp has the variation. and it was distub to other RTD temp
also. so what can I do.
Answer Posted / carl_ellis
The RTD element is ALWAYS isolated from the sheath. Dual
element RTDs should be isolated from each other.
Therefore, there should be no common electrical connection
between any wire in a dual element RTD.
The fact that a connection to one receiver (the PLC)
disturbs the other receiver's RTD reading means either
a) the RTD elements or lead wires are shorting to either
the sheath, the other RTD element or a lead wire; meaning
the RTD assembly is damaged internally.
b) the field wiring for one RTD is shorting to the field
wiring of the other RTD
Carl Ellis
Measure First
| Is This Answer Correct ? | 0 Yes | 0 No |
Post New Answer View All Answers
Explain operation of Haskel pump.
What do you know about gail?
centrifugal compressor interlock? Tell me the parameter at which compressor will trip
Explain the combusion chamber
How earthing can be checked????
i want formula for flow control.am doing project in flow control using orifice . i know value of the flow level(Q) . upstream(p1) pressure, orifice diameter(Do) , pipe diameter(Di) and oil viscosity(Vi) how can i calculate downstream pressure
How to control flow variations in magnetic flow maters..... When i will provide proper earthing?
How oil line flow measured?eplain about instruments used and working principle?
What is limitation of the ht.of the displacer of a level trol?
why we are using magnet for calibration of gas detector?
key exchanges in wpa,wpa2,tls
how to connect transmitter measuring sulfur process? 1-by using long impulse line or 2- by using coated short impulse line
i want to know the interview format fot gail, instrumentation. pls answer me in habib.sami1003@gmail.com
what is IEC code in cables & how to selecting cables?
What is zero elevation and zero suppression?