Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

1 ton AC takes how much current( starting & stable)

Answer Posted / ahmed alyassi

My friend if we assume the normal.current is 7 amps
Then due to that split ac is considered it is inductive load
The starting current would be x5 or x4 more
So . 7 times 4 =28 amps

But even if your breaker is 25 lets assume
It might not trip. Immediatly cause the delay and the amps didnt increase alot
I would recommend 32 A for 1ton or 1.5ton

Is This Answer Correct ?    20 Yes 23 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

Which level of the Transformer oil got dielectric strengh? And why?

2304


What are unstable systems?

1171


How to calculate impedance volt in Transformer?

2146


Percentage losses in power generation?

3049


how to operate and maintenance of 1500 kva diesel generator set

1860


how can service sitting be setted for MCCB?Example for sittings IR (CURRENT RATING),IS(CURRENT STARTING)IO (current operating)?

2501


WHY TERTIARY OF POWER TRANSFORMERS IS LOADED WITH EQUIPMENTS LIKE CT,PT,ISOLATOR AND CB

1954


give me atleast four differences between circuit and network

2223


Is there possible to Test Transformer for Overfluxing Capability. Or is there any firm who does Overfluxing Test on Transformer?

3177


how to select correct size of power cable for inverter duty motor

1638


WHY NUTRAL GROUND SYSTEM USED IN 33KV SYSTEM

2256


How to determine stage of Automatic Power factor controlling Relay(Apfcr)?

2219


a)In a 3-phase 4-wire circuit, a circuit breaker is selected to protect the circuit whose highest fault level is 6.6 MVA. Determine the required minimum breaking capacity in kA. (Note: Covert 3-phase power in terms of kA to find answer.) b)Using the below, determine the required minimum making capacity in kA as a “peak value”. Rate breaking capacity (Icn) ka: Icn<= 1.5 Factor = 1.41 1.5

1750


what is the electrical?

2170


I have finish diploma electronics and five years experience in electrical field in ht service how can i get c licensce or other electrical certificate

1744