flow transmitter range is 0 -500 mmwcc but the transmitter
shows 12 ma for o mmwc instead of 4 ma ...how to solve this
problem when we apply 375 mmwc it shows 16 ma
Answer Posted / dinesh
the transfer function should have been square root but the transfer function mentioned is linear which is as follows
y=mx+c where m is slope & c is the bias
to calculate slope
m={(y2-y1)/(x2-x1)} where
y2=16ma; y1=12 ma; x2=375 mmwc; x1=0 & C is 12ma at 0 mmwc
so y= (4/375)*x + 12
in order to get correct flow change the transfer function to square root in Tx
| Is This Answer Correct ? | 2 Yes | 0 No |
Post New Answer View All Answers
Do you have reference list?
Which are all the commonly used Bordon tubes in the pressure gauges. Do any one use ASTM A 312 tubes for this purpose?
How to work togather like sov,limit switch,proxy switch and booster in xv
we have a s-5 simense plc having op7 .recently on op7 showing error 1.plc not present 2. DB error frequently. can u have any solution . please send me.
Which type of pressure can be measured by primary elements?
A length of steel pipe is used to carry sea water to a desalination plant. An adequate corrosion allowance must be specified and indicated in the piping specification, which affects the _________________________ of the pipe
How u will setup SPI(2007) on Citrix Server (Thin Client Mode)? Plz Justify?
What is the procedure of calibration of Load cell?
i need some objective type questions in instrumentation
Where is wet leg is used?
you must show the examples application and give at least 4 types of transducer/sensors that can minimize the failure during the manufacturing of the resistors.
plz tell me clearly about PID.."when v have to change I value,D value,GAIN??
What is the use of each wire in three wire RTD
Please can anybody help for control valve sizing step by step procedure?
If P will increase then what will happen with PID?