i am confused about generator.
i have generator of 380 KVA that is 304 KW by that formula
KW=KVA*0.8...
then by this formula I=KW/V*1.732*0.8 the amperes are 528.673.
so that is the load which i put on one phase of generator or
this is total 3 phase load on Generator.......
Answer Posted / awais
Thanx alot sheikh... :)
but still one thing i ask u to plz tell me.....
if we run 3phase motors at this generator then maximun load
on generator is 528??
and if yes then we can say that the load on one phase is
528/3=176 amp ???
one more thing plz tell me the maximum load of generator 400
KV.A if we use it for 3phase motors...voltage 400v...
this load plz tell me in amps and also in watts....plzz its
urgentt plzzzz mann....i will be thankfull to u :)
| Is This Answer Correct ? | 0 Yes | 0 No |
Post New Answer View All Answers
In constant power region of 3-phase IM torque-speed characteristics, if frequency increases slip A does not alter B decreases C increases D none of above
Ratings of power transformer,Distribution transformer.
what would happen if reactive power (kvar)is increased (more)or decreased (less)? how much exact reactive power should be maintained? and what should be done for that
how to choose cable size with respect to load? how to convert cable size in mm2 to sq.mm?
Do you need any help with FEWA Electrical Supervisor exams?
what is the prinsiple of dc motor and construction and working ,application of dc motor.
how to design the heater in temperature control unit to heat 50KL of water?
how can service sitting be setted for MCCB?Example for sittings IR (CURRENT RATING),IS(CURRENT STARTING) I O (current operating)?
What are hrc fuses and where it is used?
There are Two questions about Steam Turbine Generator... What is HRSG bypass of LP, HP used for in power generation? In particualar, in the event that fault of HP bypass, there would be STG TRIP in operation but none on the LP bypass fault...what's the reason ?
Hi friends, i m electrical engineer i want a cdr for migration purpose so anybody have information about this then send me on jayesh_ee88@yahoo.com.please try to me
can we install HT panel & LT panel side by side or how much clearance is required ?
why steady state stability limit is greater than transient stability limit ? How it can be explained ?
we have 3 single phase transformers. how will we generate 6 supply from 3 phase supply input
Whether power factor should be high or low? Why?