IN OLTC we observed "OUT OF STEP" Alarm, we have two
different transformer, when both are in parallel this type
of alarm observed. what's the meaning of this alarm and why
it occurs???
Answer Posted / nasseem
Out of step means that the Two transformers at different tap.
i.e. TR-1 at tap n and TR-2 at tap n+1 or n-1.
And as you know the two transformers should have same tap
"if the two transformers have same tap size i.e 1.25% for
example" when it operated in parallel to prevent the
circulation current between the two transformers.
So it seems in your case if we assume TR-1 is master and
TR-2 is follower TR-1 change its tap position while TR-2
still at it is original tap.
| Is This Answer Correct ? | 13 Yes | 0 No |
Post New Answer View All Answers
Define reserve-generating capacity?
Generation of voltage for each phase are same of a turbogenerator.Although the short circuit current flow when two phase of turbogenerator are shorted(where current can't flow without potential difference),why?
how to find number of run cable laying[LT side] for transformer & alternator secondary side? [above condition for getting output power transformer to main panel side] give the example.
how to test and calculat the head and discharge in borewell compressor
how can we phase identification in a distribution line,how we recognise that which phase is coming for a house hold connection.help me............
What is the difference between electronic regulator and ordinary rheostat regulator for fans?
Describe the colour rendering properties of i) tungsten filament lamps ii) tubular fluorescent lamp
Is a direct shorth ciruit on a branch MCCB in a Low Voltage Switchboard a correct means of tesing the performance for discrimination?
The loads are connected with phase and ground then why current flow as the loads ?
I have a small system with two motors that are running on 380 vac, 60 hz. These motors are expensive and I usally get them from Brazil. I am adding another motor to the system, but I want to purchase a 480 vac, 60 hz motor to use. It will be on a VFD that is rated fro 380 thru 480. Is this posible and will I have to use a larger motor and derate it?
orifice sizing how done, checking & selection
what curve and rateing would you use for a three phase 0.75kw motor?
can any one suggest paper presentation topies for electrical engg?
TCS IS IT COMPANY THEN WHY DO THEY NEED ELECTRICAL &ELECTRONICS ENGINEERS?
Explain the operation principle, advantages and disadvantages of the following converters: a) A 12 pulse converter b) A Switch-mode inverter c) A thyristor inverter