How to calculate & connection of 900KVA generator
2 sets & load(1500A)?
How to choose cable size and ACB size for this load &
generator?
please explain me detail.
Regards,
Mr.Han
Answer Posted / ganesh
All dg 9oo*1.39a =1251a (415v , pf .8,)
1251*1.5 time full load current 1876 A
you choose 2000A breaker
300*6 sq mm2
or 225*7 SQMM2
Is This Answer Correct ? | 1 Yes | 0 No |