How to calculate & connection of 900KVA generator
2 sets & load(1500A)?
How to choose cable size and ACB size for this load &
generator?
please explain me detail.

Regards,
Mr.Han

Answer Posted / ganesh

All dg 9oo*1.39a =1251a (415v , pf .8,)
1251*1.5 time full load current 1876 A
you choose 2000A breaker
300*6 sq mm2
or 225*7 SQMM2

Is This Answer Correct ?    1 Yes 0 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

I have iti elec, 1st aid, and 5 yrs experience in 7.5 mw power plant. Am i eligeble for 11kv license in telangana state..when, how to apply for that.?

1832


How do i carry out or know the vector group of a Dyn1 and Dyn5 transformer

1544


how to Select Lighting arrester? What r the parameters to be considered for the selection of Lighting arrester ?

1189


how to calculate maximum current

1727


STATE USE OF ARC RUNNERS & SPLITTERS ?

1456






what happen when power factor of 2 parallely operated transformer become equle?

1698


what is the diference between the 4pole & 6pole DC Motors & what is advantage 6pole over the 4pole ?

1412


i am going to attaned the engineer (disign)iterview at HAL please give me duid line

1769


What is signal flow graph?

644


how much cable size required for 70 kilowatt load.

1144


If 22 KV HT line, Current transformer is 25/5 then how to calculate multiplying factor.

599


Is it possible to make a 5P10/ CT Ratio 50/1A Burden 5VA

1220


how to changeover ups in this power failur time?

1519


List some examples of renewable energy?

767


why the starting voltage drop in a cable needs to be limited?what is percentage of the voltage drop allowed during starting?

1359