In close vessel/ drum why we use d.p. transmitter of -ve
range i.e. (-)500 to 0 mmwc.
Answer Posted / venbha123
If the LP leg of the transmitter is kept dry, steam may get condensed in the LP leg because of which the level indication may be wrong. Hence We are using wet leg for LP side of the transmitter, which is initially filled with pure water. When the drum is at zero level, the pressure difference is only the head pressure acting on the LP side - that is 100% level head at LP side. Normally in DP transmitter the HP side pressure will be more than the LP side. In this case since the pressure in the LP side is more than the pressure in HP side the range is mentioned as negative. At 100% level both the head pressures at HP & LP are the same, the DP becomes zero. Therefore the range is mentioned as: from negative value to zero.
| Is This Answer Correct ? | 12 Yes | 2 No |
Post New Answer View All Answers
what is difference between HOT permit and cold permit
what is piezoelectric transducer?give an example in power plant n state its principle?
There are two chlorination tonners both are connected to two pressure swithes and the pressure switch is connected to SOV which operates the valve to changeover the tonner selection i.e if pressure one tonner goes low the other tonner should come in line if it is inautomatic selection design a circuit using relays ?
Calibration procedure for water rotameters
Type of level transmitter commnly used in Procees area are the following. a.________________This type of level transmitter works as follows
What are continuances of connecting earthing and shield of branch cables (instrument to Junction box), at the same earthing pot provided on JB? Is it ok, or may produce some problem?
What is the PLC configuration in Cement industry?
how is work pressure switch& level switch?what is the principle of this?
sir, i preparing hpcl,ongc,barc,hal exams(instrumentation engg)pls send a placement papers
CONTROL VALVE OPERATING IN MANUAL BUT NOT IN MANUAL. WHAT SHOULD BE THE PROBLEM ?
In bently nevada vibration monitoring system,what is the reason to maintain the Resistance of the probe + extension cable equal to 95 ohm? If possible explain the basic principle of measurement with detail electronic circuits.
Can combine control system for Emergency control system (ESD)and Fire & Gas System ( F & G) is possble to built and offer to client? Can such system is as per Norms in India?
Why boiler chimney area oxyden sensor fixing?
why orfice is not used for main steam flow calculation
in which principle pressure tx,level tx ,flow tx,temp tx ,control valve works?