Answer Posted / carl_ellis
These remarks refer to the use or non-use of a coriolis mass
flow meter.
A coriolis mass flow meter should not be used
- where tight shutoff valve(s) cannot be installed upstream
and downstream for the purpose of stopping all flow so that
zeroing the coriolis flow meter can be accomplished (turning
off power to the pump is NOT the same as shutting off the
flow with a ball valve). Otherwise zero shift will plague
the operation.
- in a batch operation where the meter starts empty, then
fills, and at the end might run partially filled, unless
appropriate piping is implemented to keep the Coriolis flow
meter filled with fluid all the time.
- with suspended solids in a liquid medium that are abrasive
[abrasives erode the thin tube(s)]. Reducing the flow
velocity tends to reduce abrasion and erosion. A Coriolis
tube will quickly fail when it carries suspended solids like
sand. Unless of course, frequent replacement is just the
cost of doing business.
- with a corrosive medium that will corrode the flow tube
- with medium that is above the manufacturer's stated
process medium temperature (burns up the electronics)
- with a two phase media (liquids and gas or liquids that
will flash to vapor at the operating pressures and temperatures)
- with a medium that tends to solidify (Coriolis tubes are
very thin, very light and don't like to be brush cleaned)
unless periodic solvent cleaning is feasible.
- with a medium that tends to coat the tube, unless the
required solvent or mechanical cleaning is feasible.
- where the flow tube is subject to mechanical vibration
- when the meter is mounted where the flow is vertical down
- when the meter is mounted in horizontal piping at a high
point where gas/air can be trapped at a high point
- where the pressure drop across the flowmeter is higher
than the process can tolerate
- when the location is too close to another coriolis meter;
where each meter can be affected by crosstalk vibrations
from the other coriolis meter.
- hazardous or classified zones where the Coriolis' power
requirements exclude it from meeting hazardous area approval.
- for flow measurement requiring pipe sizes larger than
commercial coriolis meters (10 or 12" in 2014)
Carl Ellis
Measure First
| Is This Answer Correct ? | 4 Yes | 0 No |
Post New Answer View All Answers
Can any body help to get Rsemulator 5000 free from internet if possible then give me any link or any help .
Questions on flow meters,few questions on HART protocol,
pls suggest suitable MOC of diaphragm for pressure measurement of UREA grade solution service fluid.
please tell no. & add. of consultancy who recruit me in power plant as instrumen engg. present i m working in power plant as ass.t instrument engg. thanku mahesh 09226562826
hye SAM acn u send your e mail id, so that i can solve my query through e mail?
hello friends, can you please send me the model paper or question paper to be prepared for hpcl examinations????????? You can mail me at rahim_here@yahoo.com waiting for your reply........... help me .. plz.....
sir, give me placement papers and interview quistion of birla group company of copper.
can any send me a forbes marshall dtron 316 manual
this site is owned by an nonsense
Can any one tell me what type of question asked for instrumentation and control interview panel??? pls mail ramashankar.goel@gmail.com
What are the key features of a Distributed Control System? describing the various layers (sensor through to business system interfaces) as well as the hardware, software and security aspects of the DCS.
please any body have most important data for study for saudi aramco test of instrument QC thanks email shahnaveedullah@gmail.com
please send me some question papers of HPCL aptitude test ?? please send it to bipinb.28@gmail.com ...
A PLC is programmed to drive three motors A, B and C as follows : After running motor A for an hour, motor B should get ON and motor A should get OFF. And after running motor B for an hour, motor C should get ON and motor B should get OFF. And after running motor C for an hour, motor A should get ON and motor C should get OFF. (That is, a cyclic repetition with time period one hour) Now, the second condition is: If any motor gone faulty and is tripped, the consecutive motor should get ON and the faulty (tripped) motor should be eliminated from cyclic repetition. The remaining two motors should bear the cyclic repetition of one hour each. (For healthy motor take logic as high and for tripped motor take logic as low) Now, the third condition is: When motor A load(Amps) exceeds 60% of its rated load, motor B should get ON in parallel to motor A. And when both motors A & B are running in parallel, and if their load exceeds 60% of their rated load, motor C should also start in parallel to A & B. [Here the cyclic repetition is eliminated, until their loads become normal(40%)] [Take logic high(1) for load at 60% and logic low(0) for load at 40%] Now draw a flow chart or a ladder diagram to fulfill the above condition.
any body who gone thru recent iocl interview.INSTRUMENTATION questions. I need.