Answer Posted / carl_ellis
These remarks refer to the use or non-use of a coriolis mass
flow meter.
A coriolis mass flow meter should not be used
- where tight shutoff valve(s) cannot be installed upstream
and downstream for the purpose of stopping all flow so that
zeroing the coriolis flow meter can be accomplished (turning
off power to the pump is NOT the same as shutting off the
flow with a ball valve). Otherwise zero shift will plague
the operation.
- in a batch operation where the meter starts empty, then
fills, and at the end might run partially filled, unless
appropriate piping is implemented to keep the Coriolis flow
meter filled with fluid all the time.
- with suspended solids in a liquid medium that are abrasive
[abrasives erode the thin tube(s)]. Reducing the flow
velocity tends to reduce abrasion and erosion. A Coriolis
tube will quickly fail when it carries suspended solids like
sand. Unless of course, frequent replacement is just the
cost of doing business.
- with a corrosive medium that will corrode the flow tube
- with medium that is above the manufacturer's stated
process medium temperature (burns up the electronics)
- with a two phase media (liquids and gas or liquids that
will flash to vapor at the operating pressures and temperatures)
- with a medium that tends to solidify (Coriolis tubes are
very thin, very light and don't like to be brush cleaned)
unless periodic solvent cleaning is feasible.
- with a medium that tends to coat the tube, unless the
required solvent or mechanical cleaning is feasible.
- where the flow tube is subject to mechanical vibration
- when the meter is mounted where the flow is vertical down
- when the meter is mounted in horizontal piping at a high
point where gas/air can be trapped at a high point
- where the pressure drop across the flowmeter is higher
than the process can tolerate
- when the location is too close to another coriolis meter;
where each meter can be affected by crosstalk vibrations
from the other coriolis meter.
- hazardous or classified zones where the Coriolis' power
requirements exclude it from meeting hazardous area approval.
- for flow measurement requiring pipe sizes larger than
commercial coriolis meters (10 or 12" in 2014)
Carl Ellis
Measure First
| Is This Answer Correct ? | 4 Yes | 0 No |
Post New Answer View All Answers
hi my name is rakesh patel i just complited my be in instrumentation & control now i am going to working as a validation engineer in a poject department so what is a scope in a future as a validation engginer ? what line is good for me can any bady give me complete solution please? your regard rakesh patel
How to Calibrate Temperature Switch in field
How to Calibrate Interface Level Troll in field
what is difference between fork type and capacitance type level switch. where it is using
What is difference of fanuc alpha series 16i and 18i controller.also what is differnce betn TC and MC controller
Hi Friends , i need one urgent help , i am preparing for M.tech entrance examination , i need some obejective questions related to instrumentation field. where can i get those ? can anyone help me pls ?
What is the difference between mmwc and mmwg?
I need to know steps to Calibration Valve Guard......
How to check vortex flow meter is in good condition while we do not having calibration setup?
How do you identify between actual alarm and false alarm in a Temperature Transmitter in SCADA based Control System
how to rectify the poor signal strength in utrasonic digtial flow meter ,model:ge digital xce868i
Explain the burnout feature.
if in a level tx height is given, how u calculate the ranges of the tx?
what is the reset offset and control system in instrumentation
3. Differentiate between ultrasonic flowmeter and radar type flow meter.