Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

Where we cant instal mass flow meter.

Answer Posted / carl_ellis

These remarks refer to the use or non-use of a coriolis mass
flow meter.

A coriolis mass flow meter should not be used

- where tight shutoff valve(s) cannot be installed upstream
and downstream for the purpose of stopping all flow so that
zeroing the coriolis flow meter can be accomplished (turning
off power to the pump is NOT the same as shutting off the
flow with a ball valve). Otherwise zero shift will plague
the operation.

- in a batch operation where the meter starts empty, then
fills, and at the end might run partially filled, unless
appropriate piping is implemented to keep the Coriolis flow
meter filled with fluid all the time.

- with suspended solids in a liquid medium that are abrasive
[abrasives erode the thin tube(s)]. Reducing the flow
velocity tends to reduce abrasion and erosion. A Coriolis
tube will quickly fail when it carries suspended solids like
sand. Unless of course, frequent replacement is just the
cost of doing business.

- with a corrosive medium that will corrode the flow tube

- with medium that is above the manufacturer's stated
process medium temperature (burns up the electronics)

- with a two phase media (liquids and gas or liquids that
will flash to vapor at the operating pressures and temperatures)

- with a medium that tends to solidify (Coriolis tubes are
very thin, very light and don't like to be brush cleaned)
unless periodic solvent cleaning is feasible.

- with a medium that tends to coat the tube, unless the
required solvent or mechanical cleaning is feasible.

- where the flow tube is subject to mechanical vibration

- when the meter is mounted where the flow is vertical down

- when the meter is mounted in horizontal piping at a high
point where gas/air can be trapped at a high point

- where the pressure drop across the flowmeter is higher
than the process can tolerate

- when the location is too close to another coriolis meter;
where each meter can be affected by crosstalk vibrations
from the other coriolis meter.

- hazardous or classified zones where the Coriolis' power
requirements exclude it from meeting hazardous area approval.

- for flow measurement requiring pipe sizes larger than
commercial coriolis meters (10 or 12" in 2014)

Carl Ellis
Measure First

Is This Answer Correct ?    4 Yes 0 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

What is first echo & echo window in radar type level transmitter?

1697


How do bending tubing provide better measurement than using tubing fittings such as elbows?

1943


what is the vital subject for scoring bhel exam&what is the question pattern

2418


Q- Control problem are mainly classified in _____ types. a-)4 b-)3 c-)6 d-)nono of these Few of them i know is 1- regulator type problem (eg- Air conditioner) 2- tracking problem (eg missile trcking problem) 3- sybernatics 4- optimal control problem

2128


䑰ҕ䔈ҕ䖠ҕ䘰ҕ䛀ҕ䝐ҕ䟐ҕ䢐ҕ䥐ҕŹ

1954


you are on site,the plant trips,you are approached by operations,what do you do?

2249


hiii.... can any one provide me previous years question paper of hindustan petroleum for instrumentation engineering???

1987


Questions on flow meters,few questions on HART protocol,

2000


what does the ratio 800-400-300-200/1-1-1-1-1 in the specification of current transformer indicates?

2541


Hook up resistance decade box to temp.transmitter.

2301


Make Heater Process Logic.

2118


Specify ideal accuracy of flow element like orifice plate, Ventury, Annubar. Ultrasonic flow meter etc.

1922


What is Positive Calibration and Negative Calibration?

2251


what is moisture probe? What are there types? What is there working principle and how they works? guys this is one of technical question I had ask in interview. If you know its answer please let me know. The interviewers were more interested in microwave moisture probe, so if you find its any link please just forward me on my mail id.avinash1200@gmail.com Thanks in advance.

2056


How the sizing of the analog signal cable is calculate?

2532