Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

I want formula to calculate cable size as per load given in
kw & amp.I searched many sites but didn't right answer.Plz
reply me asap.

Answer Posted / engr.muhammad younas khan

CABLE SIZING FORMULAS:-
1ST STEP CALCULATE THE VOLTAGE DROP (Vd).
(1 ph.) Vd= 2 x I x L x P.F/(K x Area mm2)
(3 ph.) Vd=1.732 x I x L/(KxArea mm2)
where:-
I:- Load current
L:- Length of the conductor.(in meters)
K:- 58 for copper conductor and 36 for aluminum conductor.
2 for single phase and sqrt 3 for three phase.
____________________________________________________________
2nd step.
AREA mm2 = 2 X I X L /(K x Vd) (FOR SINGLE PHASE)
AREA mm2 = 1.732 x I x L/(K x Vd)(for three phase)
____________________________________________________________
FORMULAS DESIGNED BY
ENGR.
MUHAMMAD YOUNAS KHAN
M.Sc.Engg.,MIEE(UK)
NEAR KEEKER WALI MASJID.
MOHELLAH LAKER MANDI
WAZIRABAD CITY,PUNJAB
PAKISTAN

Is This Answer Correct ?    5 Yes 1 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

how to revers the direction of single phase motor

1004


distribution transformer de-rating formula on over limit iron losses  

2348


Explain the working of any one cutting machine

1154


How one can check the MAIN of a house wiring ?

2022


What is transient response?

1180


what is accuracy ? in any meters , coils accuracy . how can u defined that ?

2488


HOW DO I CALCULATE THE SETTINGS FOR THE DIFFERENTIAL PROTECTION OF A 12kV/6.6kV, 6MVA,DYN11 XMER WITH PRIMARY SIDE CTR 400/1 AND SEC SIDE CTR 600/1?

2676


A 400KVA transformer has 400 Hz frequency. If the frequency is changed to 50 Hz, then what will be the new KVA rating?

1852


We have Diesel generator of 200KW. fuel consumption is always same,even connected light load or full load. Is it right?

2236


On a 3 winding transformer YNynd11, how do you apply REF protection to the Delta tertiary winding that is supplying auxiliaries to a substation?

4418


What is excitation in case of dc motor?

1223


how to determine Sq.mm size of finolex power cables.

2046


PLEASE TELL ME ABOUT QUESTION PAPER OF UPCL ENTERENCE EXAM.

8052


75 kw motor take 45 amp in no load delta in star 10 amp but in load it will take 160 amp but IR velue of winding above 500 at 1kw ph to earth and ph to ph. what problem it should be?

3785


Determine a suitable number of slors and conductors per slot for the starter 1 winding of a 3 phase, 3300 V. SO Hz 300 rpm alternator. The diameter is 2.3 m

2883