Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

Why we use 250 ohm resister in series
hart communicator?

Answer Posted / carl_ellis

HART communications requires a minimum of 230 ohms to
develop a sufficient voltage drop for the 1200 baud FSK HART
signal to be 'seen' by a HART communicator/modem.

The capacitance in a DC power supply acts as a low pass
filter which filters/strips off the FSK HART data.
Additional loop resistance is needed for HART communications
to take place.

If there is insufficient loop resistance, the HART
communicator/modem will fail to establish HART communications.

In normal field work, it is assumed that the analog input
to which the field instrument is wired will provide the
minimum resistance necessary. Most DCS analog inputs have
an input resistance of 250 ohms. But not all devices do.

And when bench testing/configuring HART instruments it is
not uncommon to connect a DC power supply, but not an analog
input. A HART communicator/modem will not work with just a
power supply powering a HART field instrument. The loop
requires a minimum of 230 ohms.

A 250 ohm resistor is commonly used for a bench
test/configuration because they're commonly available in the
instrument shop.

Carl Ellis
Measure First

Is This Answer Correct ?    15 Yes 1 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

Boolean algebra

2114


the whole paper was based on Transducers..questions like define repeatability, error,accuracy,precision..den there were many q. on the conversion of Pa to mmHg and other units.. also..der wer few Q. on some level sensors(with diagram)

2006


Make Heater Process Logic.

2051


Explain the mechanism behind the turbine meter.

1061


types of cable..? Use of every types of cable..?

2092


2. What is ultrasonic flowmeter?

4981


Why all the drains(Gland sealing,ESV,Casing inlet etc) are directly connected to the flash tank instead of hotwell of the condensor in the power plant? My Email Id:naba02222@gmail.com

2239


what about your moleg in pogrees with company

2218


what is interface level and how it is calibrate?

2288


What is defferent betwen ESP &PCP PUMP .HOW IT IS WORK?

2417


How is PH sensor works ?

1915


Give 2 application of quartz crystal used for process parameter measurement.

1968


What is surge and how is it prevented, what is the purpose of bypass valve across AS valve.

1841


what is IEC code in cables & how to selecting cables?

1726


who's take first position in process in the timing of new installation flow transmitter and control vavle. give the answer with logical trick.

5072