Can DP transmitter with orifice plate works on Beta ratio
0f 0.3 and differential pressure of 100 MMWC in liquid
service application?
Answer Posted / carl_ellis
An orifice plate (OP) creates a pressure drop in the flow
stream.
The question is whether an orifice plate 'works'. Works how?
An orifice plate will always 'work' by creating a pressure
drop; the proper questions are whether the permanent
pressure loss is excessive, whether the orifice plate has
been 'sized' for a specific medium at correct design
conditions, and whether the pressure drop (DP) is adequate
for instrumentation that senses the DP.
Orifice plates typically drop 100 inches water column at
100% flow rate, about 25 times the DP of 100mm water column.
A DP of 100mm water column at 100% flow rate is more
typical of an averaging pitot tube than an orifice plate. A
full scale flow rate of 100mm w.c. requires a low range
pressure transmitter, or one with a high turndown ratio.
A 0.3 Beta is acceptable.
Carl Ellis
Measure First
Is This Answer Correct ? | 2 Yes | 0 No |
Post New Answer View All Answers
Im having problems with interfase betwen SPI v7.0 and SPPID v5.05. Previous versions of Intools shoul be fixed with SPPIDproj.ocx file. It was necessary to replace this file with one that allows the connection between different versions of SPPID. It is necessary in the current version to do the same?Thanks
how to work static pressure sensore how to work dpt
What is sensitivity in vibration probes..?
Make Heater Process Logic.
What are the charcterstics of a P&ID controller block for Governor speed raise or lower for a load sharing functionality between 4 Gas turbines in droop mode.
What is standard of DCS panel design?and what is step of DCS panel design?wiring and type of connector(screw or DB connector)
What are the application of bernoulli’s theorem?
What are different types of control valves?
what does it mean an active front end in vfd plz explain it briefly
Somebody can explain me about >Critical Loops, calibrations, ESD critical Loop checks, Logic Diagram / Cause & Effect checks for ESD loops,
If relative y axis vibration sensor is by passed, and relative x axis and absolute sensor is left working. how much monitoring i would have risked?
sir, i preparing hpcl,ongc,barc,hal exams(instrumentation engg)pls send a placement papers
you must show the examples application and give at least 4 types of transducer/sensors that can minimize the failure during the manufacturing of the resistors.
can we create an interrupt in plc through scada?
How to Calibrate Flow Switch in field