For testing 33kv cable hipot testing. How much kv we have to
Apply .Give in details.
Answer Posted / michael aliganga
CABLE FACTORY AC TEST VOLTAGE =2E+1kV= 2X35+1= 71kV
DC HIPOT TEST:
CABLE INSTALLATION TEST DURING AND AFTER = ET= EF X 1.8 X 0.8
ET = 71 X 1.8 X 0.8 = 102kV, ICEA DC FIELD TEST VOLTAGE
(ICEA S-97-682) IS 100 kV FOR 35 KV SHIELDED POWER CABLE.
EF=CABLE MANUFACTURERS RECOMMENDED FACTORY AC TEST VOLTAGE
IF NOT AVAIABLE USE 2E+1KV
1.8 AC TO DC CONVERSION FACTOR (QUITE COMMON)
0.8 CONVERSION FACTOR FOR DERATING FROM FACTORY TESTING TO
ACCEPTANCE TESTING.
Is This Answer Correct ? | 3 Yes | 2 No |
Post New Answer View All Answers
How to Calculate the Fault Level of Electrical Installation
Explain marx circuit.
If we impress a dc voltage of 230 V on an unloaded 230 V, 50 Hz transformer it wi A give high secondary voltage B burn out C give secondary voltage as per K D none of these
what is the ms flat constant for calculating earth mat design calculation?
difference between high and low impedance BUS BAR relay??
what will happen if the prime mover on the field excitation of the on-coming generator fails?Explain.
any application of back emf
what is the diff. between x'mer , isolation x'mer & ultra-isolation x'mer ?????????????
Why it need to form a capcitor when it not been in use from three or two year. Plz describe it technically.
why -48 volts dc used in telecommucation
What will be the size of copper cable (each for 3 phase and 1 neutral) from Service connection Kit-Kat to Panel Board (i.e. to main switch) for a 6 pole 3-phase AC induction motor of 200 H.P. capacity? Amp-255 A, Frequency:- 1450 rpm.
how to calculate transformer turn primary & secondary side 11kv to 420v
State nyquist stability criterion.
WHAT IS AIR GAP VALUE IN MM FOR A 11KV BUSHING OF 11KV/440V DISTRIBUTION TRANSFORMER. AND AIR GAP VALUE OF 25 KV BUSHING OF AT TRANSFORMER OF 25 KV TRACTION. WHAT IS THE CALCULATION FOR THE AIR GAP PERMITTED FOR BUSHINGS AT DIFFERENT VOLTAGES.
Hello sir i m student of gtu .what is idp.