Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

For testing 33kv cable hipot testing. How much kv we have to
Apply .Give in details.

Answer Posted / michael aliganga

CABLE FACTORY AC TEST VOLTAGE =2E+1kV= 2X35+1= 71kV
DC HIPOT TEST:
CABLE INSTALLATION TEST DURING AND AFTER = ET= EF X 1.8 X 0.8
ET = 71 X 1.8 X 0.8 = 102kV, ICEA DC FIELD TEST VOLTAGE
(ICEA S-97-682) IS 100 kV FOR 35 KV SHIELDED POWER CABLE.

EF=CABLE MANUFACTURERS RECOMMENDED FACTORY AC TEST VOLTAGE
IF NOT AVAIABLE USE 2E+1KV
1.8 AC TO DC CONVERSION FACTOR (QUITE COMMON)
0.8 CONVERSION FACTOR FOR DERATING FROM FACTORY TESTING TO
ACCEPTANCE TESTING.

Is This Answer Correct ?    3 Yes 2 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

What is zero of the system?

1154


what are the specifications we must look at to select a relay for any capacity motor?

2081


If Neutral Grounding Resistor (GR) failed/shorted. Is it repairable.

1685


why various test are performed on electrical panels & power cables before commissioning on site & what are these test???

2049


if 6 earth pit value is 1.5 ohm then what should be the number of earth pit to make the value .8 ohm

2327


Where can i get practical knowledge of solar system?

1515


Power Factor Correction Panel (Manual & Automatic)

2290


Why is water motor not taking the pressure? what is the problem?

1631


why current flow to the opposite direction of flow of electrons???????????

2221


I have a small system with two motors that are running on 380 vac, 60 hz. These motors are expensive and I usally get them from Brazil. I am adding another motor to the system, but I want to purchase a 480 vac, 60 hz motor to use. It will be on a VFD that is rated fro 380 thru 480. Is this posible and will I have to use a larger motor and derate it?

2024


how to carried out tan delta test in 11 KV alternator ?

3129


A jet of fluid strikes a plate What was the force required to counter it?

1916


EXPLAIN WHY THE SURGE CURRENT RATING OF AN MCCB OR CIRCUIT BREAKER DECREASES WITH INCREASE IN THE RATING OF MCCB OR CIRCUIT BREAKER.

2068


Do you know what is dry-out test in x'mer

2711


what is the basic need of domestic loads 1- voltage 2- current

2174