Dear all... I have 1 0-400 duplex type RTD, I connected the
A side to the temperature indicator and B side to the PLC
panel, but when I have observed then found that The PLC side
temp has the variation. and it was distub to other RTD temp
also. so what can I do.pls help me

Answer Posted / carl_ellis

An offset in readings from separate RTD's can indicate
- a difference in calibration of the analog input devices
- a bad RTD element, one that has drifted out of spec
- a common ground issue with ground loops between the analog
input devices

An RTD is supposed to be ungrounded and the two RTD's in a
duplex element are supposed to be electrically isolated from
one another, so it is unlikely the ground loop is unlikely
unless poor wiring of the extension wire or head wiring has
created a connection to ground.

If you're complaining about a small difference of the
indicated temperatures, then get out your cal gear and cal
the inputs.

To check for a bad RTD, I'd take an ohmmeter and see if any
leg on the A side has any connection to the B side by
disconnecting the wiring from each analog input and check
the resistance. If there's a low resistance, it indicates
some connection from A to B. If the extension wires are
then disconnected and the resistance is checked on the RTD
lead wires and the resistance remains, then it's a bad RTD.
If the resistance goes high (open circuit) then the
extension wire is shorting or making a low resistance
connection somewhere.

Carl Ellis
Measure First

Is This Answer Correct ?    1 Yes 2 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

how radio frequency level probes works with its controller ? what is its principle ? pls give me brief explanation?

1394


our kks tagging is crossing more than 12 character please suggest how to take tags in the DCS

1661


why orfice is not used for main steam flow calculation

1601


Why flow/pressure transmitter before control valve?

1054


How does your previous experience relate to the job you are applying for ?

1554






How to find out the current of two motors having same power consumption but different RPM?

1533


what is The specifications for oriface instalation

1604


What is the difference between modbus,fieldbus & profibus

1871


what is output of FOUNDATION FIELD BUS transmitter

1694


What are the uses of orifice plates?

614


what is a vortex flow meter,mass flow meter and electromagnetic flow meter.particular use of this.means in which condition particular meter is used.

1726


How can measure flow in oil line?which type of transmitter is generally used?

3536


What are different types of orifice plates? State their uses.

632


What materials are used in thermo wells?

614


DEAR SIR/MADAM MY NAME IS ARKAPROVA BHATTACHARYYA.I AM A FRESHER INSTRUMENTATION ENGINEER.CAN YOU PLEASE SEND SOME QUESTION PAPERS OF GRADUATE ENGINEER TRAINEE EXAM OF DVC(DAMODAR VALLY CORPORATION).MY EMAIL IDs ARE arka_aec@rediffmail.com.

1457