IF we have 500kva transformer & know the current on HT & LT side, how can we consider for its breaker?
Answer Posted / maze one
S = I x V x sq. root of 3
where:
S = Apparent Power, VA
I = Current, A
V = Voltage, V
note : use sq. root of 3 if the system is 3 phase
let's say Voltage = 460V @ Secondary Side
I = (500,000 VA)/(460V)(sq. root of 3)
I = 1,882.66 A
you may multiply the safety factor by 125% to 250%
or using inversed time circuit breaker by 250%
I will use 125% only, that is safe
I = 1882.66 x 125%
I = 2,353.325 AT
| Is This Answer Correct ? | 0 Yes | 1 No |
Post New Answer View All Answers
what is the excess air in furnace
What difference between ref protection and differential protection ?
What is the minimum value of hfe for the oscillations in transistorized rc phase shift oscillator?
how we calculate the dick for a pole?
what is mind in cable
what is the relationship between current&voltage in practical purpose ?
What kinds of decision are made about CT from it's Knee point(voltage & current)?
what is the safe meggar values for motor, transformer HT, LT and Cables? IF we want to replace I/C bay at our 220 kv substation which is of 140 mw load capacity bay to be replaced by 400 mw capacity bay.other than CT(1200/1) what are the other equipment i have to replace. why we generally use 3.5 core cable or in other word 1/2 core for neutral and also confirm me that in balance conditiob(3 phase)current in neutral will zero
What are the protections for safe running of electric generator?
100 MVA 3-phase alternator with earthed neutral has a reactance of 5 ohms per phase. what will be the fault MVA of generator.
Haw to check conductivity of budbar
what's the difference between abs/inc encoders. apart from the position remembrance what are all the other differences. and what's mean by grey code.
WHY BREAKER ARE USED IN SUBSTATIONS?
Define what is power quality meter ?
how a.c. genarator control power factor when its conected to grid supply by incrising or decresing excitation voltage.