Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

What happens instead of using 3 phase, if we give loop of
single phase to all three phases ??

Answer Posted / 7anoter4

If the supply system was 3 phase with neutral the single-
phase consumers [lighting, single-phase motors and so on]
could work [you have to check the other two phase are
disconnected at first].The current on the remaining phase
will rise since all load will stay on this single phase [it
depends on how was the load distributed per phase]. The
three-phase motor will not work at all-no start- no current
for ungrounded stator winding and high current for grounded
one].

If the supply system was 3 phases without neutral nothing
would work [you supply one-phase without return through
neutral].

Is This Answer Correct ?    3 Yes 2 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

What is non-minimum phase transfer function?

1227


State angle criterion.

1063


how to interlock 3 nos MCCBs using under voltage coil. please provide me circuit diagram?

2550


how to find the voltage's of a transmission line plzz help with pictures i am not able to understand

1296


What is the suitable transmission voltage?

1024


I want d.g.set our company

1815


what is the advantages of having in-built acvvvf (without seperate inverter in the control panel)in the drive system of elevators?

3316


what is the difference between megger and earth resister ??

1768


What is the IS standard for MCCB to be use (As per capacity of AMP)& for ACB also.

1961


What is mason's gain formula?

1222


is it necessary to earth the rmu before cutting off the transformer winding?if yes why?

1872


How 3 phase invertor works?

1989


Discuss about gear cutting machines.

1159


for what voltage will reactive power be largest in 380 kv line : a) 375kv b)380kv c)385kv

1410


standard earthing rating for power line..

2065