We operate a 10 Mw facility and we have been experiencing
several trips due to fluctuations on the MVAR? We have
checked all issues related to the AVR and we have found all
OK? Can anyone help us? The grid voltage, internal voltage,
all regular parameters look ok. MVAR fluctuate and there it
goes the unit? What could be happening? Thanks!
Answer Posted / a.j.pailwan
Please check CT connections, CT Specifications and
saturation of particularly B phase as this CT feed back is
used in AVR during PF control mode while pareller with grid.
Is This Answer Correct ? | 0 Yes | 0 No |
Post New Answer View All Answers
Do Phase angle measurement have any application in freq/harmonics measurement? If so how?
Why you want to join non technical field when you are an engineer?
high voltage transformer input voltage,current and amps rating..distributed transformer input voltage,current and amps rating...
Pleae send me last 5 years of Question book about RRB chennai.
Why dry type cast resin transformers tap link blast in HV side while power shut down times on load?
how withstand of hi-pot test outputs of transformer wire 2.5mm
im working in one private compeny in gujarat. i was complet diploma electric in 2010 from gujarat technical board. now i want electric supervisor licence in gujarat but i dont't know when i apply? plz give me address of the licence dippartment office in gujarat. gandhinagar
Difference of induction motor & servo motor ??
how brushed dc motor operating ?
Block diagram of Power line communication?
Define pole pitch?
What is the difference between alternator and generator?
Can you please explain creepage distance in detail, for a 6.6kV cable head what must the distance be and how do you determine it?
what is the basic construction diffrance between servo motor ans sqiralcage induction motor
What is the effect of pi controller on the system performance?