We operate a 10 Mw facility and we have been experiencing
several trips due to fluctuations on the MVAR? We have
checked all issues related to the AVR and we have found all
OK? Can anyone help us? The grid voltage, internal voltage,
all regular parameters look ok. MVAR fluctuate and there it
goes the unit? What could be happening? Thanks!
Answer Posted / a.j.pailwan
Please check CT connections, CT Specifications and
saturation of particularly B phase as this CT feed back is
used in AVR during PF control mode while pareller with grid.
| Is This Answer Correct ? | 0 Yes | 0 No |
Post New Answer View All Answers
which protection used in power plant?
compare between starting charactristics of synchronous motor with those of 3Q Squirrel cage induction motor
what transformer we used normally and upto which kva?
what do w do when the output of generator is fluctuating?
Both generator parallel condition shared load equally but one genrator taking ampere more than the other what are all the causes to make like this
if in 3-phase system voltage=440V,frequency=60Hz, current=400A. then if it is single phase then current=? and if it is single phasing then current=?
What is the fault or needs to be done when frequency in ac drives is not changing?
What are the different types of hydro schemes?
What current position are you holding in your current company?
What is the function of NER and NET?
How many types of electric motors are there?
What is the simplest formula to calculate the rotor diameter of a synchronous generator?
how the characterstics of control valve being done
WHAT IS THE MEANING OF BALANCED / UNBALANCED IN STABILIZER TYPES.
when the time of backcharging the transformer three phases only enough or three phase with neutral is must.from these which one is the best one.