Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

One 200 V, 100 W bulb is connected in series with primary of
a 200 V, 10 kVA transformer. If its secondary is
kept open circuited, then the bulb would have
(1) Full brightness (2) Poor brightness
(3) A little less than full brightness (4) More than full
brightness...explain

Answer Posted / ajayiet

when transformer secondary
is open it is at no load means
only no load current will flow
to supply the losses .but luk at
the rating of machine 10000
va so full load current is 10
kva/200 v i.e. 50 amp.now no
load current is 2 to 6 percent
of full load current i.e. 1 to 3
amp.resistance of lamp is 200
ohms so at no load wattage
i^2R is from 200 to 600
watt.so bulb will be
damaged.option is more
appropriate.

Is This Answer Correct ?    2 Yes 5 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

how mass curve differs from hydrograph.

1800


plz send me HPCL apptitude paper.. maulik_elect@yahoo.co.in

2094


Why delta star trformers are used for lighting loads?

1189


Can we put 3 layers of cable tray while installing tray

2404


can a 150 kva 3 phase 440v/230V delta-wye step down transformer can be use as step up transfoermer with connected loads at 440v side?

1735


why the India electrical supply transmission loss is high when compare to us

1988


how to calculate slip ring induction motor stator and rotor currents??

2268


What are the advantages of autotransformer?

1221


What are the difference between CT/PT operated Meter and RRAMR Meter for HT/LT application?

2614


In ht capacitor ckt we are using LBS Panel it having isolator with fuse, one of HT fuse flash over, so what is reason behind this event.

2093


can we find the inductance of a induction motor?

1999


Difference of induction motor & servo motor ??

1828


I Need standard operation procedure(SOP)for 500kva Oil type transformer oil filtration & Procedure for IR value checking.

2899


in single phase converter, the no.of scr's conducting during overlap a)1 b)2 c)3 d)4

2072


What is the Load Capacity of Panther conductor (0.2) and dog conductor (0.2) 

2835